2018-03-12 12:03:06 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN |
| WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON |
| THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS |
| CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED |
| 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT |
| SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD |
| CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT |
| CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. |
| PER FBC PL 1108.1 |
| |
| 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB |
| BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE |
| GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. |
| OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE |
| CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER |
| FBC ACC 604.5.1 |
| |
| 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH |
| DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL |
| 405.3.1 |
| |
| 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB |
| BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR |
| TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN |
| MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS |
| WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL |
| DETAILS. PER FBC ACC 609.4 |
| |
| 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM |
| OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 |
| MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 |
| |
| 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR |
| SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 |
| |
| 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE |
| WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 |
| |
| 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER |
| CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 |
| |
| 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR |
| ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? |
| OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL |
| DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC |
| 604.5.1 |
| |
| 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE |
| SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF |
| THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE |
| CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT |
| BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC |
| 609.4 |
| |
| 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING |
| KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 |
| |
| 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON |
| BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE |
| ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM |
| 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? |
| WALL THICKNESS. PER FBC ENERGY C404.4 |
| |
| 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS |
| BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE |
| COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK |
| IT SHALL CONNECT TO INTAKE OF THE BOILER. PER |
| MANUFACTURE INSTALL GUIDE |
| |
| 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| FBC PL 316.1.3 |
| |
| 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER |
| ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON |
| THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. PER FBC PL 1003.2 |
| |
| 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON |
| BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS |
| DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM |
| CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE |
| ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. |
| |
| 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC |
| IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE |
| SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS |
| TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN |
| AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY |
| ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON |
| THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, |
| 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER |
| DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT |
| AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC |
| VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| |
| 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 |
| |
| 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| FOOD CODE |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEASE PROVIDE PLUMBING FIXTURE COUNT BREAK DOWN |
| WITH OCCUPANT LOAD FOR EACH AREA PER OCCUPANT TYPE ON |
| THE 1ST + 2ND FLOOR, THE ONE THAT WAS ON SHT. GN-1 IS |
| CONFUSING UNDER THE BUSINESS OCCUPANCY IT LIST REQUIRED |
| 2 TOILETS FOR MEN AND WOMEN PROVIDED 1 TOILET THAT |
| SEEMS LESS THE REQUIRED AMOUNT. PLEASE CLARIFY PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 2. IF THE COVERED ENTRY CANOPY HAS A PARAPET THAT WOULD |
| CAUSING WATER TO POND UP IF THE MAIN STORM DRAIN GOT |
| CLOGGED AN OVERFLOW DRAIN OR SCUPPER WILL BE REQUIRED. |
| PER FBC PL 1108.1 |
| |
| 3. 3. SHT. A-406-A DETAIL #1 NOTES AN ADA TRANSFER TUB |
| BUT IT SHOWS ROLLS IN SHOWER PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 4. SHT. A-407, 408, 409 DETAIL #1, A THE END OF THE |
| GRAB BAR ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. |
| OF 54? OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE |
| CHECK ALL DETAILS SHOWING THE SIDE WALL GRAB BAR. PER |
| FBC ACC 604.5.1 |
| |
| 5. SHT. A-407, 408, 409, PLEASE SHOW THE DEPTH |
| DIMENSION OF THE STANDARD TOILET STALL. PER FBC PL |
| 405.3.1 |
| |
| 6. SHT. A-407, 408, 409, 414 DETAIL B, C, F THE GRAB |
| BARS SHALL BE SHOWN TO BE MEASURED FROM FINISHED FLOOR |
| TO THE TOP OF THE GRIPPING SURFACE THEY ARE SHOWN |
| MEASURED 36? TO THE CENTER OF THE BAR IF INSTALLED THIS |
| WAY THEY WILL NOT BE CODE COMPLIANT PLEASE CHECK ALL |
| DETAILS. PER FBC ACC 609.4 |
| |
| 7. SHT. A-407, 408, 409, 414 DETAILS E, C, B, THE RIM |
| OF THE LAVATORY IS SHOWN OVER 34? IT SHALL BE 34 |
| MAX PLEASE CHECK ALL DETAILS. PER FBC ACC 606.3 |
| |
| 8. SHT. A 414 PLEASE SHOW THE REQUIRED CLEAR FLOOR |
| SPACE FOR THE TRANSFER SHOWER. PER FBC ACC 608.2.1 |
| |
| 9. SHT. A 414 THE SEAT IN THE TRANSFER SHOWER SHALL BE |
| WITHIN 3? OF THE FRONT OF THE SHOWER. PER FBC ACC 610.3 |
| |
| 10. SHT. A 414 PLEASE SHOW COMPLIANCE WITH SHOWER |
| CONTROLS AND SPAY UNIT. PER FBC ACC 608.5.1 |
| |
| 11. SHT. 417 DETAIL # 1, H, D THE END OF THE GRAB BAR |
| ON THE SIDE WALL OF THE TOILET SHALL BE A MIN. OF 54? |
| OFF THE REAR WALL IT IS SHOWN AT 48? PLEASE CHECK ALL |
| DETAILS SHOWING THE SIDE WALL GRAB BAR. PER FBC ACC |
| 604.5.1 |
| |
| 12. SHT. 417 DETAIL #C, D,E,H THE GRAB BARS SHALL BE |
| SHOWN TO BE MEASURED FROM FINISHED FLOOR TO THE TOP OF |
| THE GRIPPING SURFACE THEY ARE SHOWN MEASURED 36? TO THE |
| CENTER OF THE BAR IF INSTALLED THIS WAY THEY WILL NOT |
| BE CODE COMPLIANT PLEASE CHECK ALL DETAILS. PER FBC ACC |
| 609.4 |
| |
| 13. SHT. A-4.15 PLEASE SHOW COMPLIANCE FOR THE WARMING |
| KITCHEN SINK SHALL COMPLY WITH FBC ACC 606.2 AND 606.3 |
| |
| 14. SHT. P-102 SANITARY PIPE NOT SHOWN FOR COMMON |
| BATHROOMS ON 2ND FLOOR PLEASE CLARIFY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 15. SHT P-104 SHOWS A TRANSFER TUB FOR ROOM 1009 THE |
| ACCESSIBLE ROOM MATRIX LIST ROLLS IN SHOWER FOR ROOM |
| 1009 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 16. THE HOT WATER PIPING AND RECERC PIPING SHALL BE 1? |
| WALL THICKNESS. PER FBC ENERGY C404.4 |
| |
| 17. SHT. P-601 CONDENSING WATER HEATER SCHEDULE IS |
| BLANK PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 18. SHT. P-503 THE WATER HEATER PIPING DETAIL SHOWS THE |
| COLD SUPPLY CONNECTING TO THE INLET OF THE STORAGE TANK |
| IT SHALL CONNECT TO INTAKE OF THE BOILER. PER |
| MANUFACTURE INSTALL GUIDE |
| |
| 19. PROVIDE SE (SESCO) SOVENT TITE RUFF DESIGN MANUAL. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 20. PROVIDE A PLAN REVIEW AND APPROVAL OF THE SE |
| (SESCO) TITE RUFF SOVENT SYSTEM FOR THIS PROJECT. PER |
| FBC PL 316.1.3 |
| |
| 21. PLEASE PROVIDE EXPANDED SANITARY AND WATER |
| ISOMETRICS FOR THE COMMON AREA BATHROOMS AND KITCHEN ON |
| THE 1ST AND 2ND FLOOR. PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 22. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. PER FBC PL 1003.2 |
| |
| 23. P- 701 IT APPEARS THAT THE VENT FOR THE COMMON |
| BATHROOMS ARE CONNECTING TO THE SOVENT AERATORS THIS |
| DOES NOT COMPLY WITH SOVENT DESIGN MANUAL VENTS FROM |
| CONVENTIONAL SYSTEMS SHALL VENT SEPARATELY THROUGH THE |
| ROOF OR CONNECT SEPARATELY TO THE SOVENT STACK. |
| |
| 24. SHT. A-0.01 THE SHEET INDEX LIST A STORM ISOMETRIC |
| IT IS MISSING FROM SUBMITTED DRAWINGS, IN THE PRE |
| SUBMITTAL MEETING WE WERE TOLD THE EXISTING STORM WAS |
| TO REMAIN IF THIS IS STILL THE CASE PLACE NOTE ON PLAN |
| AND PROVIDE DRAWINGS WITH DETAILS FOR COVERED ENTRY |
| ROOF DRAINS. PLEASE CLARIFY PER WPB AMEND TO FBC |
| 107.3.5.1.3(13) |
| |
| 25. SHT. P 701 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| MATCH THE FLOOR PLAN AND STACKS ON SHT. P-702. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| 26. PLEASE SIZE THE PIPING AND LABEL THE FIXTURES ON |
| THE SANITARY AND WATER ISOMETRIC DRAWINGS SHTS. P-701, |
| 702, 703, 704. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 27. SHT. P 703 THE ISOMETRIC DRAWING IS TO CONGESTED TO |
| DETERMINE CODE COMPLIANCE FOR CLARIFICATION JUST SHOW |
| PIPING FOR 1ST AND 2ND FLOOR WITH THE STACKS LABEL TO |
| MATCH THE FLOOR PLAN AND STACKS ON SHT. P-704. PER WPB |
| AMEND TO FBC 107.3.5.1.3(13) |
| |
| 28. SHT. P-503 DETAIL #2 AND THE GAS WATER HEATER |
| DIRECT VENT COMBUSTION DETAIL SHOW TWO DIFFERENT VENT |
| AND INTAKE SYSTEMS PLEASE PROVIDE A SIT SPECIFIC |
| VENTING DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| |
| 29. THE POOL BATHROOMS SHALL COMPLY WITH FBC PL 403.6 |
| |
| 30. SANITARY PIPING OVER THE KITCHEN AREA SHALL BE |
| SHIELDED TO INTERCEPT POTENTIAL DRIPS OR LEAKS. PER US |
| FOOD CODE |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |