2018-02-26 15:42:42 | 1ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION |
| CODES |
| PERMIT #18020254 |
| 2/23/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) ELECTRONIC SIGNATURES ARE REQUIRED ON THE MECHANICAL |
| PLANS, AND THE FOLLOWING LIST OF DOCUMENTS: ENERGYGAUGE |
| COMPLIANCE FORM, THE AC LOAD CALCULATIONS, AND THE |
| VENTILATION CALCULATIONS- SECTIONS 61G15-23.002 AND |
| 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. |
| |
| 2) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA |
| FOR OAU- 1 & 2, AND WSHP 1-3. TO HELP EXPEDITE THE |
| REVIEW, PLEASE IDENTIFY THE OTHER SYSTEMS IN THE REPORT |
| SO THEY MATCH THE IDENTIFICATIONS IN THE SCHEDULES ON |
| SHEET M-601. |
| |
| 3) AC CALCULATIONS: PLEASE CLARIFY WHY NO OUTDOOR |
| VENTILATION DATA IS PROVIDED, AND WHY THE O/A DB/WB LOW |
| TEMPS FOR THE COMMON AREAS AND KITCHEN ARE NOT |
| CONSISTENT WITH ASHRAE 183 OR ACCA MANUAL N. |
| |
| 4) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH C407 |
| FBC-17 ENERGY CONSERVATION. PLEASE NOTE THE HOTEL ROOM |
| AC SYSTEMS ARE EXEMPT FROM THE REPORT. |
| |
| 5) PLEASE REFER TO BUILDING REVIEW COMMENT # 2C: THE |
| TWO PRESSURIZED INTERIOR EXIT STAIRWAYS #111 AND 114 |
| ARE EXITING INTO COMMON CORRIDORS AND NOT INTO EXIT |
| DISCHARGES OR EXIT PASSAGEWAYS AS REQUIRED BY SECTIONS |
| 1023.2 AND 1023.11.1 FBC-17 BUILDING. IN ORDER FOR THE |
| EXISTING MEANS OF EGRESS SYSTEM TO BE IN COMPLIANCE |
| WITH THE CURRENT CODES, THE GROUND FLOOR CORRIDORS THAT |
| ARE FORMING THE PATHS OF TRAVEL TO THE EXTERIOR OF THE |
| BUILDING, MAY HAVE TO BE RE- CONSTRUCTED AS EXIT |
| PASSAGEWAYS AND BECOME EXTENSIONS OF THE SMOKEPROOF |
| ENCLOSURES- STAIRWAYS #111 AND 114. IN ADDITION THE |
| PASSAGEWAYS SHALL BE PRESSURIZED EQUALLY TO THE |
| PRESSURIZATION RATES PROVIDED FOR THE STAIRWAYS. |
| CURRENTLY THERE IS NO SMOKE CONTROL RATIONAL ANALYSIS |
| PROVIDED FOR THE PROPOSED PROJECT TO VERIFY THE CURRENT |
| SYSTEM DESIGN WILL PROVIDE A TENABLE ENVIRONMENT FOR |
| THE EVACUATION AND RELOCATION OF THE OCCUPANTS. PLEASE |
| REVIEW SECTION 513 IN ENTIRETY AND PROVIDE A RATIONAL |
| ANALYSIS REPORT THAT ENCOMPASSES ALL COMPLIANCES AS |
| OUTLINED IN THE SUB-SECTIONS. ALL MECHANICAL COMPONENTS |
| AND EQUIPMENT SUCH AS FANS, DUCTS, DAMPERS ETC. SHALL |
| CORRESPOND WITH THE SPECIFICATIONS LISTED IN THE |
| REPORT. THE REPORT SHALL INCLUDE, BUT NOT BE LIMITED TO |
| THE FOLLOWING REQUIREMENTS LISTED IN SECTION 513. |
| |
| 513.6 PRESSURIZATION METHOD. |
| THE PRIMARY MECHANICAL MEANS OF CONTROLLING SMOKE SHALL |
| BE BY PRESSURE DIFFERENCES ACROSS SMOKE BARRIERS. |
| MAINTENANCE OF A TENABLE ENVIRONMENT IS NOT REQUIRED IN |
| THE SMOKE CONTROL ZONE OF FIRE ORIGIN. |
| 513.6.1 MINIMUM PRESSURE DIFFERENCE. |
| THE MINIMUM PRESSURE DIFFERENCE ACROSS A SMOKE BARRIER |
| SHALL BE 0.05-INCH WATER GAGE (12.4 PA) IN FULLY |
| SPRINKLERED BUILDINGS. |
| IN BUILDINGS PERMITTED TO BE OTHER THAN FULLY |
| SPRINKLERED, THE SMOKE CONTROL SYSTEM SHALL BE DESIGNED |
| TO ACHIEVE PRESSURE DIFFERENCES NOT LESS THAN TWO TIMES |
| THE MAXIMUM CALCULATED PRESSURE DIFFERENCE PRODUCED BY |
| THE DESIGN FIRE. |
| 513.6.2 MAXIMUM PRESSURE DIFFERENCE. |
| THE MAXIMUM AIR PRESSURE DIFFERENCE ACROSS A SMOKE |
| BARRIER SHALL BE DETERMINED BY REQUIRED DOOR-OPENING OR |
| CLOSING FORCES. THE ACTUAL FORCE REQUIRED TO OPEN EXIT |
| DOORS WHEN THE SYSTEM IS IN THE SMOKE CONTROL MODE |
| SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| BUILDING. OPENING AND CLOSING FORCES FOR OTHER DOORS |
| SHALL BE DETERMINED BY STANDARD ENGINEERING METHODS FOR |
| THE RESOLUTION OF FORCES AND REACTIONS. THE CALCULATED |
| FORCE TO SET A SIDE-HINGED, SWINGING DOOR IN MOTION |
| SHALL BE DETERMINED BY: |
| (EQUATION 5-1) |
| WHERE: |
| A = DOOR AREA, SQUARE FEET (M2). |
| D = DISTANCE FROM DOOR HANDLE TO LATCH EDGE OF DOOR, |
| FEET (M). |
| F = TOTAL DOOR OPENING FORCE, POUNDS (N). |
| FDC = FORCE REQUIRED TO OVERCOME CLOSING DEVICE, POUNDS |
| (N). |
| K = COEFFICIENT 5.2 (1.0). |
| W = DOOR WIDTH, FEET (M). |
| P = DESIGN PRESSURE DIFFERENCE, INCHES (PA) WATER GAGE. |
| |
| 513.6.3 PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS. |
| WHERE STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED, |
| SUCH PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION |
| 513 AS SMOKE CONTROL SYSTEMS, IN ADDITION TO THE |
| REQUIREMENTS OF SECTIONS 909.20 OF THE FLORIDA BUILDING |
| CODE, BUILDING AND THE FLORIDA FIRE PREVENTION CODE. |
| |
| 513.10 EQUIPMENT. |
| EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS, |
| AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE |
| FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE |
| EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS |
| INDICATES, AND AS APPROVED BY THE CODE OFFICIAL. |
| |
| 513.10.1 EXHAUST FANS. |
| COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED |
| BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE |
| TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS |
| TEMPERATURE RISE SHALL BE COMPUTED BY: |
| |
| (EQUATION 5-2) |
| WHERE: |
| C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE, |
| BTU/LB F (KJ/KG K). |
| M = EXHAUST RATE, POUNDS PER SECOND (KG/S). |
| QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW). |
| TA = AMBIENT TEMPERATURE, F (K). |
| TS = SMOKE TEMPERATURE, F (K). |
| EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE |
| ASSURANCE OF ADEQUATE DILUTION AIR. |
| |
| 513.10.2 DUCTS. |
| DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF |
| WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO |
| WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH |
| SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND |
| SUPPORTED IN ACCORDANCE WITH CHAPTER 6. DUCTS SHALL BE |
| LEAK TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE IN |
| ACCORDANCE WITH NATIONALLY ACCEPTED PRACTICES. MEASURED |
| LEAKAGE SHALL NOT EXCEED 5 PERCENT OF DESIGN FLOW. |
| RESULTS OF SUCH TESTING SHALL BE A PART OF THE |
| DOCUMENTATION PROCEDURE. DUCTS SHALL BE SUPPORTED |
| DIRECTLY FROM FIRE-RESISTANCE-RATED STRUCTURAL ELEMENTS |
| OF THE BUILDING BY SUBSTANTIAL, NONCOMBUSTIBLE |
| SUPPORTS. |
| EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF |
| VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED |
| FIRE-RESISTANCE-RATED MATERIALS. |
| |
| 513.10.3 EQUIPMENT, INLETS AND OUTLETS. |
| EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE |
| UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL |
| FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS |
| TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR |
| FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO |
| LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE |
| BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR |
| ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD. |
| |
| 513.10.4 AUTOMATIC DAMPERS. |
| AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH |
| THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM, |
| SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF |
| APPROVED RECOGNIZED STANDARDS. |
| |
| 513.10.5 FANS. |
| IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS |
| SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR |
| THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING |
| TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE |
| BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE, |
| ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER?S |
| FAN CURVES SHALL BE PART OF THE DOCUMENTATION |
| PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY |
| NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE |
| STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING |
| CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE |
| OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS) |
| AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW. |
| MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR |
| OF 1.15. |
| |
| 513.11 STANDBY POWER. |
| THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH STANDBY |
| POWER IN ACCORDANCE WITH SECTION 2702 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 513.11.1 EQUIPMENT ROOM. |
| THE STANDBY POWER SOURCE AND ITS TRANSFER SWITCHES |
| SHALL BE IN A ROOM SEPARATE FROM THE NORMAL POWER |
| TRANSFORMERS AND SWITCH GEAR AND VENTILATED DIRECTLY TO |
| AND FROM THE EXTERIOR. THE ROOM SHALL BE ENCLOSED WITH |
| NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED FIRE |
| BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OF |
| THE FLORIDA BUILDING CODE, BUILDING OR HORIZONTAL |
| ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711 |
| OF THE FLORIDA BUILDING CODE, BUILDING, OR BOTH. |
| |
| 513.11.2 POWER SOURCES AND POWER SURGES. |
| ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON |
| VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH |
| UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO |
| SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF |
| THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES |
| SHALL BE SUITABLY PROTECTED BY CONDITIONERS, |
| SUPPRESSORS OR OTHER APPROVED MEANS. |
| |
| 513.12 DETECTION AND CONTROL SYSTEMS. |
| FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR |
| OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR |
| ELEMENTS THEREOF SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTION 907 OF THE FLORIDA BUILDING CODE, BUILDING. |
| SUCH SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT |
| COMPLYING WITH UL 864 AND LISTED AS SMOKE CONTROL |
| EQUIPMENT. |
| |
| 6) PLEASE PROVIDE STAIR AND ELEVATOR PRESSURIZATION |
| RISER DRAWINGS SHOWING THE LOCATIONS OF BAROMETRIC |
| RELIEF DAMPS AND HOISTWAY VENTS. |
| |
| 7) CONCERNING SECTION 513.11.1 LISTED ABOVE, PLEASE |
| SHOW THE LOCATION OF THE GENERATOR TRANSFER SWITCHES. |
| |
| 8) SHEET M-106: SEPARATE PERMITS ARE REQUIRED FOR THE |
| KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK IN |
| COOLER AND FREEZER, HOWEVER AN AIR BALANCE CALCULATION |
| IS REQUIRED PER SECTION 508.1.2: |
| 508.1.2AIR BALANCE. |
| DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN |
| VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM |
| INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN |
| OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND |
| REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET |
| EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR |
| AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE |
| PLUS THE NET EXFILTRATION. |
| |
| 9) M-106: AS STATED IN THE PREVIOUS COMMENT, A SEPARATE |
| PERMIT IS REQUIRED FOR THE KITCHEN HOOD AND EXHAUST |
| SYSTEM, HOWEVER IT IS IMPORTANT TO NOTE AT THIS TIME OF |
| THE MAIN PERMIT AND PLANS THAT COMPLIANCE WITH SECTION |
| C403.2.8 FBC-17 ENERGY CONSERVATION IS REQUIRED. |
| C403.2.8 KITCHEN EXHAUST SYSTEMS |
| REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST |
| HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE |
| HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR |
| DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF |
| THE FOLLOWING: |
| 1. THE VENTILATION RATE REQUIRED TO MEET THE SPACE |
| HEATING OR COOLING LOAD. |
| 2. THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER |
| AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS |
| CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT |
| REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS |
| RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION |
| OF ADJACENT SPACES. |
| WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS |
| GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A |
| FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A |
| NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE |
| WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST |
| RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY |
| WITH ONE OF THE FOLLOWING: |
| 1. NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR |
| SHALL BE TRANSFER AIR THAT WOULD OTHERWISE BE |
| EXHAUSTED. |
| 2. DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75 |
| PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS |
| THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT |
| AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY |
| TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION |
| AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE, |
| EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND |
| IDLE. |
| 3. LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT |
| RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON |
| NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW. |
| WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER |
| APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM |
| ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL |
| BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE |
| DUTY RATING UNDER THE HOOD OR HOOD SECTION. |
| EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE |
| REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE |
| EXHAUSTED. |
| |
| 10) M-101: VERIFY THAT EXHAUST HOOD GREASE DUCT IS NOT |
| TERMINATING ABOVE A WALKWAY OR ANYPLACE THAT COULD |
| CREATE A PUBLIC NUISANCE OR FIRE HAZARD- SECTION |
| 506.3.13.2. PROVIDE THE HEIGHT OF THE OUTLET ABOVE THE |
| ADJOINING GRADE. |
| |
| 11) M-101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY TRUNKS OF WSHP-1-1 AND WSHP-1-4 PER SECTION |
| 606.2.1. PLEASE NOTE AN EXEMPTION CAN BE APPLIED TO 1-4 |
| IF MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS |
| NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| |
| 12) M-101 & M-102: THE OUTSIDE AIR DUCT DOES NOT APPEAR |
| TO BE MAKING DIRECT CONNECTIONS TO WSHP-1-5, 1-6, AND |
| 1-7- PLEASE CLARIFY. |
| |
| 13) M-101: PLEASE CLARIFY HOW SUPPLY AIR TO THE LOBBY, |
| MARKET PLACE, RECEPTION AREAS ETC. IS BEING RETURNED TO |
| WSHP-1-3- SECTION 601.6. |
| |
| 14) M-101: PROVIDE DRYER EXHAUST PLANS AND DETAILS PER |
| SECTION 504, AND SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE DRYERS REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD. |
| |
| 15) M-101: THE LAUNDRY SERVICE ROOM IS MISLABELED AS |
| THE CHEF'S OFFICE. |
| |
| 16) M-101: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL |
| GAS-FIRED KITCHEN COOKING APPLIANCES AND SUBMIT |
| EQUIPMENT CUT SHEETS REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD- SECTIONS 304 AND 623.1 FBC-17 FUEL |
| GAS. PLEASE NOTE THERE DOES NOT APPEAR TO BE FOOD |
| SERVICE PLANS INCLUDED IN THE SETS- PLEASE PROVIDE |
| THEM. |
| |
| 17) M-102: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| SUPPLY TRUNK OF WSHP-2-2 PER SECTION 606.2.1. |
| |
| 18) M-102: FIRE DAMPERS NOT SHOWN AT A) THE O/A AND E/A |
| DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM |
| WALLS. B) THE S/A DUCT PENETRATION THROUGH THE |
| FIRE-RATED WALL AT ROOM 226/227. C) THE 8" E/A DUCT |
| PENETRATION THROUGH THE FIRE-RATED 227/231 WALL- |
| SECTION 607.5.2 & 607.5.3 |
| |
| 19) M-102: INDICATE HOW ACCESS FOR SERVICE AND |
| REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL |
| CEILINGS WILL BE PROVIDED- SECTION 306. |
| |
| 20) M-102: SHOW HOW SUPPLY AIR FROM WSHP-2-2 AND |
| WSHP-C-2 IS BEING RETURNED INTO THE MECHANICAL ROOM- |
| SECTION 601.6. |
| |
| 21) M-103: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A |
| DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM |
| WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-3 |
| PENETRATING THE FIRE-RATED 323/324/325 WALLS.- SECTION |
| 607.5.2 & 607.5.3 |
| |
| 22) M-103: INDICATE HOW ACCESS FOR SERVICE AND |
| REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL |
| CEILINGS WILL BE PROVIDED- SECTION 306. |
| |
| 23) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-3 IS BEING |
| RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6. |
| |
| 24) M-104: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A |
| DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM |
| WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-10 |
| PENETRATING THE FIRE-RATED 1023/1025 WALLS- SECTION |
| 607.5.2 & 607.5.3 |
| |
| 25) M-103: INDICATE HOW ACCESS FOR SERVICE AND |
| REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL |
| CEILINGS WILL BE PROVIDED- SECTION 306. |
| |
| 26) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-10 IS BEING |
| RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6. |
| |
| 27) M-401: PROVIDE AN ENLARGED PLAN OF THE GENERATOR |
| THAT PROVIDES DETAILS FOR THE ENGINE AND RADIATOR |
| EXHAUST SYSTEMS, AND THE ROOM VENTILATION. CLARIFY IF |
| THE GENERATOR HAS A BELLY TANK FOR DIESEL FUEL OR IF |
| THERE IS TO BE A SEPARATE TANK AND TANK ROOM PROVIDED. |
| SUBMIT MANUFACTURER'S SPECIFICATIONS REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD. |
| |
| 28) M-501: PROVIDE WSHP INSTALLATION DETAILS. |
| |
| 29) M-502: THE RTU ATTACHMENT DETAIL TO THE CURB IS FOR |
| A CARRIER UNIT, HOWEVER THE SYSTEMS SELECTED ARE TRANE- |
| PLEASE CORRECT. |
| |
| 30) M-601: PLEASE PROVIDE COMPLETE WINDLOAD ENGINEERING |
| FOR INSTALLATION OF THE OAU'S, THE ROOF AND WALL FANS, |
| THE ROOFTOP DUCTWORK, AND THE WATER PIPING. PLEASE |
| INCLUDE THE WIND LOAD DESIGN CRITERIA AND DETAILS FOR |
| ATTACHING THE CURBS AND BRACKETS TO THE ROOF STRUCTURE, |
| AND THE UNITS TO THE CURBS AND BRACKETS- SECTION |
| 301.15. |
| |
| 31) PROVIDE A CONDENSATE DISPOSAL PLAN AND RISER |
| DRAWING- SECTION 307. |
| |
| 32) PROVIDE FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE |
| NOA'S FOR ALL EXTERIOR EXHAUST AND O/A INLET LOUVERS, |
| AC STANDS AND WALL BRACKETS, DUCT AND PIPE STANDS AND |
| BRACKETS- RULE 9N-03 FAC. |
| |
| 32) REQUIRED SUBMITTALS TO BE REVIEWED AND APPROVED BY |
| THE DESIGNER OF RECORD: PRODUCT APPROVALS AND NOA?S, |
| SMOKE CONTROL FANS, FIRE AND FIRE/SMOKE DAMPERS, |
| MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, BOILER AND |
| WATER HEATERS, COOKING APPLIANCES, PLENUM RATED ACCESS |
| PANELS FOR ABOVE CEILING HEAT PUMPS AND FANS, |
| GENERATOR, FIRE CAULKING AND FIRE WRAPPING. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |