Plan Review Notes
Plan Review Notes For Permit 18020254
Permit Number 18020254
Review Stop M
Sequence Number 1
Notes
Date Text
2018-02-26 15:42:421ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #18020254
 2/23/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ELECTRONIC SIGNATURES ARE REQUIRED ON THE MECHANICAL
 PLANS, AND THE FOLLOWING LIST OF DOCUMENTS: ENERGYGAUGE
 COMPLIANCE FORM, THE AC LOAD CALCULATIONS, AND THE
 VENTILATION CALCULATIONS- SECTIONS 61G15-23.002 AND
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE ENERGYGAUGE REPORT IS MISSING COMPLIANCE DATA
 FOR OAU- 1 & 2, AND WSHP 1-3. TO HELP EXPEDITE THE
 REVIEW, PLEASE IDENTIFY THE OTHER SYSTEMS IN THE REPORT
 SO THEY MATCH THE IDENTIFICATIONS IN THE SCHEDULES ON
 SHEET M-601.
  
 3) AC CALCULATIONS: PLEASE CLARIFY WHY NO OUTDOOR
 VENTILATION DATA IS PROVIDED, AND WHY THE O/A DB/WB LOW
 TEMPS FOR THE COMMON AREAS AND KITCHEN ARE NOT
 CONSISTENT WITH ASHRAE 183 OR ACCA MANUAL N.
  
 4) PROVIDE A COMMISSIONING PLAN IN ACCORDANCE WITH C407
 FBC-17 ENERGY CONSERVATION. PLEASE NOTE THE HOTEL ROOM
 AC SYSTEMS ARE EXEMPT FROM THE REPORT.
  
 5) PLEASE REFER TO BUILDING REVIEW COMMENT # 2C: THE
 TWO PRESSURIZED INTERIOR EXIT STAIRWAYS #111 AND 114
 ARE EXITING INTO COMMON CORRIDORS AND NOT INTO EXIT
 DISCHARGES OR EXIT PASSAGEWAYS AS REQUIRED BY SECTIONS
 1023.2 AND 1023.11.1 FBC-17 BUILDING. IN ORDER FOR THE
 EXISTING MEANS OF EGRESS SYSTEM TO BE IN COMPLIANCE
 WITH THE CURRENT CODES, THE GROUND FLOOR CORRIDORS THAT
 ARE FORMING THE PATHS OF TRAVEL TO THE EXTERIOR OF THE
 BUILDING, MAY HAVE TO BE RE- CONSTRUCTED AS EXIT
 PASSAGEWAYS AND BECOME EXTENSIONS OF THE SMOKEPROOF
 ENCLOSURES- STAIRWAYS #111 AND 114. IN ADDITION THE
 PASSAGEWAYS SHALL BE PRESSURIZED EQUALLY TO THE
 PRESSURIZATION RATES PROVIDED FOR THE STAIRWAYS.
 CURRENTLY THERE IS NO SMOKE CONTROL RATIONAL ANALYSIS
 PROVIDED FOR THE PROPOSED PROJECT TO VERIFY THE CURRENT
 SYSTEM DESIGN WILL PROVIDE A TENABLE ENVIRONMENT FOR
 THE EVACUATION AND RELOCATION OF THE OCCUPANTS. PLEASE
 REVIEW SECTION 513 IN ENTIRETY AND PROVIDE A RATIONAL
 ANALYSIS REPORT THAT ENCOMPASSES ALL COMPLIANCES AS
 OUTLINED IN THE SUB-SECTIONS. ALL MECHANICAL COMPONENTS
 AND EQUIPMENT SUCH AS FANS, DUCTS, DAMPERS ETC. SHALL
 CORRESPOND WITH THE SPECIFICATIONS LISTED IN THE
 REPORT. THE REPORT SHALL INCLUDE, BUT NOT BE LIMITED TO
 THE FOLLOWING REQUIREMENTS LISTED IN SECTION 513.
  
 513.6 PRESSURIZATION METHOD.
 THE PRIMARY MECHANICAL MEANS OF CONTROLLING SMOKE SHALL
 BE BY PRESSURE DIFFERENCES ACROSS SMOKE BARRIERS.
 MAINTENANCE OF A TENABLE ENVIRONMENT IS NOT REQUIRED IN
 THE SMOKE CONTROL ZONE OF FIRE ORIGIN.
 513.6.1 MINIMUM PRESSURE DIFFERENCE.
 THE MINIMUM PRESSURE DIFFERENCE ACROSS A SMOKE BARRIER
 SHALL BE 0.05-INCH WATER GAGE (12.4 PA) IN FULLY
 SPRINKLERED BUILDINGS.
 IN BUILDINGS PERMITTED TO BE OTHER THAN FULLY
 SPRINKLERED, THE SMOKE CONTROL SYSTEM SHALL BE DESIGNED
 TO ACHIEVE PRESSURE DIFFERENCES NOT LESS THAN TWO TIMES
 THE MAXIMUM CALCULATED PRESSURE DIFFERENCE PRODUCED BY
 THE DESIGN FIRE.
 513.6.2 MAXIMUM PRESSURE DIFFERENCE.
 THE MAXIMUM AIR PRESSURE DIFFERENCE ACROSS A SMOKE
 BARRIER SHALL BE DETERMINED BY REQUIRED DOOR-OPENING OR
 CLOSING FORCES. THE ACTUAL FORCE REQUIRED TO OPEN EXIT
 DOORS WHEN THE SYSTEM IS IN THE SMOKE CONTROL MODE
 SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING. OPENING AND CLOSING FORCES FOR OTHER DOORS
 SHALL BE DETERMINED BY STANDARD ENGINEERING METHODS FOR
 THE RESOLUTION OF FORCES AND REACTIONS. THE CALCULATED
 FORCE TO SET A SIDE-HINGED, SWINGING DOOR IN MOTION
 SHALL BE DETERMINED BY:
 (EQUATION 5-1)
 WHERE:
 A = DOOR AREA, SQUARE FEET (M2).
 D = DISTANCE FROM DOOR HANDLE TO LATCH EDGE OF DOOR,
 FEET (M).
 F = TOTAL DOOR OPENING FORCE, POUNDS (N).
 FDC = FORCE REQUIRED TO OVERCOME CLOSING DEVICE, POUNDS
 (N).
 K = COEFFICIENT 5.2 (1.0).
 W = DOOR WIDTH, FEET (M).
 P = DESIGN PRESSURE DIFFERENCE, INCHES (PA) WATER GAGE.
  
 513.6.3 PRESSURIZED STAIRWAYS AND ELEVATOR HOISTWAYS.
 WHERE STAIRWAYS OR ELEVATOR HOISTWAYS ARE PRESSURIZED,
 SUCH PRESSURIZATION SYSTEMS SHALL COMPLY WITH SECTION
 513 AS SMOKE CONTROL SYSTEMS, IN ADDITION TO THE
 REQUIREMENTS OF SECTIONS 909.20 OF THE FLORIDA BUILDING
 CODE, BUILDING AND THE FLORIDA FIRE PREVENTION CODE.
  
 513.10 EQUIPMENT.
 EQUIPMENT SUCH AS, BUT NOT LIMITED TO, FANS, DUCTS,
 AUTOMATIC DAMPERS AND BALANCE DAMPERS SHALL BE SUITABLE
 FOR THEIR INTENDED USE, SUITABLE FOR THE PROBABLE
 EXPOSURE TEMPERATURES THAT THE RATIONAL ANALYSIS
 INDICATES, AND AS APPROVED BY THE CODE OFFICIAL.
  
 513.10.1 EXHAUST FANS.
 COMPONENTS OF EXHAUST FANS SHALL BE RATED AND CERTIFIED
 BY THE MANUFACTURER FOR THE PROBABLE TEMPERATURE RISE
 TO WHICH THE COMPONENTS WILL BE EXPOSED. THIS
 TEMPERATURE RISE SHALL BE COMPUTED BY:
  
 (EQUATION 5-2)
 WHERE:
 C = SPECIFIC HEAT OF SMOKE AT SMOKE-LAYER TEMPERATURE,
 BTU/LB F (KJ/KG K).
 M = EXHAUST RATE, POUNDS PER SECOND (KG/S).
 QC = CONVECTIVE HEAT OUTPUT OF FIRE, BTU/S (KW).
 TA = AMBIENT TEMPERATURE, F (K).
 TS = SMOKE TEMPERATURE, F (K).
 EXCEPTION: REDUCED TS AS CALCULATED BASED ON THE
 ASSURANCE OF ADEQUATE DILUTION AIR.
  
 513.10.2 DUCTS.
 DUCT MATERIALS AND JOINTS SHALL BE CAPABLE OF
 WITHSTANDING THE PROBABLE TEMPERATURES AND PRESSURES TO
 WHICH THEY ARE EXPOSED AS DETERMINED IN ACCORDANCE WITH
 SECTION 513.10.1. DUCTS SHALL BE CONSTRUCTED AND
 SUPPORTED IN ACCORDANCE WITH CHAPTER 6. DUCTS SHALL BE
 LEAK TESTED TO 1.5 TIMES THE MAXIMUM DESIGN PRESSURE IN
 ACCORDANCE WITH NATIONALLY ACCEPTED PRACTICES. MEASURED
 LEAKAGE SHALL NOT EXCEED 5 PERCENT OF DESIGN FLOW.
 RESULTS OF SUCH TESTING SHALL BE A PART OF THE
 DOCUMENTATION PROCEDURE. DUCTS SHALL BE SUPPORTED
 DIRECTLY FROM FIRE-RESISTANCE-RATED STRUCTURAL ELEMENTS
 OF THE BUILDING BY SUBSTANTIAL, NONCOMBUSTIBLE
 SUPPORTS.
 EXCEPTION: FLEXIBLE CONNECTIONS, FOR THE PURPOSE OF
 VIBRATION ISOLATION, THAT ARE CONSTRUCTED OF APPROVED
 FIRE-RESISTANCE-RATED MATERIALS.
  
 513.10.3 EQUIPMENT, INLETS AND OUTLETS.
 EQUIPMENT SHALL BE LOCATED SO AS TO NOT EXPOSE
 UNINVOLVED PORTIONS OF THE BUILDING TO AN ADDITIONAL
 FIRE HAZARD. OUTDOOR AIR INLETS SHALL BE LOCATED SO AS
 TO MINIMIZE THE POTENTIAL FOR INTRODUCING SMOKE OR
 FLAME INTO THE BUILDING. EXHAUST OUTLETS SHALL BE SO
 LOCATED AS TO MINIMIZE REINTRODUCTION OF SMOKE INTO THE
 BUILDING AND TO LIMIT EXPOSURE OF THE BUILDING OR
 ADJACENT BUILDINGS TO AN ADDITIONAL FIRE HAZARD.
  
 513.10.4 AUTOMATIC DAMPERS.
 AUTOMATIC DAMPERS, REGARDLESS OF THE PURPOSE FOR WHICH
 THEY ARE INSTALLED WITHIN THE SMOKE CONTROL SYSTEM,
 SHALL BE LISTED AND CONFORM TO THE REQUIREMENTS OF
 APPROVED RECOGNIZED STANDARDS.
  
 513.10.5 FANS.
 IN ADDITION TO OTHER REQUIREMENTS, BELT-DRIVEN FANS
 SHALL HAVE 1.5 TIMES THE NUMBER OF BELTS REQUIRED FOR
 THE DESIGN DUTY WITH THE MINIMUM NUMBER OF BELTS BEING
 TWO. FANS SHALL BE SELECTED FOR STABLE PERFORMANCE
 BASED ON NORMAL TEMPERATURE AND, WHERE APPLICABLE,
 ELEVATED TEMPERATURE. CALCULATIONS AND MANUFACTURER?S
 FAN CURVES SHALL BE PART OF THE DOCUMENTATION
 PROCEDURES. FANS SHALL BE SUPPORTED AND RESTRAINED BY
 NONCOMBUSTIBLE DEVICES IN ACCORDANCE WITH THE
 STRUCTURAL DESIGN REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING. MOTORS DRIVING FANS SHALL NOT BE
 OPERATING BEYOND THEIR NAMEPLATE HORSEPOWER (KILOWATTS)
 AS DETERMINED FROM MEASUREMENT OF ACTUAL CURRENT DRAW.
 MOTORS DRIVING FANS SHALL HAVE A MINIMUM SERVICE FACTOR
 OF 1.15.
  
 513.11 STANDBY POWER.
 THE SMOKE CONTROL SYSTEM SHALL BE SUPPLIED WITH STANDBY
 POWER IN ACCORDANCE WITH SECTION 2702 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 513.11.1 EQUIPMENT ROOM.
 THE STANDBY POWER SOURCE AND ITS TRANSFER SWITCHES
 SHALL BE IN A ROOM SEPARATE FROM THE NORMAL POWER
 TRANSFORMERS AND SWITCH GEAR AND VENTILATED DIRECTLY TO
 AND FROM THE EXTERIOR. THE ROOM SHALL BE ENCLOSED WITH
 NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OF
 THE FLORIDA BUILDING CODE, BUILDING OR HORIZONTAL
 ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711
 OF THE FLORIDA BUILDING CODE, BUILDING, OR BOTH.
  
 513.11.2 POWER SOURCES AND POWER SURGES.
 ELEMENTS OF THE SMOKE MANAGEMENT SYSTEM RELYING ON
 VOLATILE MEMORIES OR THE LIKE SHALL BE SUPPLIED WITH
 UNINTERRUPTIBLE POWER SOURCES OF SUFFICIENT DURATION TO
 SPAN 15-MINUTE PRIMARY POWER INTERRUPTION. ELEMENTS OF
 THE SMOKE MANAGEMENT SYSTEM SUSCEPTIBLE TO POWER SURGES
 SHALL BE SUITABLY PROTECTED BY CONDITIONERS,
 SUPPRESSORS OR OTHER APPROVED MEANS.
  
 513.12 DETECTION AND CONTROL SYSTEMS.
 FIRE DETECTION SYSTEMS PROVIDING CONTROL INPUT OR
 OUTPUT SIGNALS TO MECHANICAL SMOKE CONTROL SYSTEMS OR
 ELEMENTS THEREOF SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 907 OF THE FLORIDA BUILDING CODE, BUILDING.
 SUCH SYSTEMS SHALL BE EQUIPPED WITH A CONTROL UNIT
 COMPLYING WITH UL 864 AND LISTED AS SMOKE CONTROL
 EQUIPMENT.
  
 6) PLEASE PROVIDE STAIR AND ELEVATOR PRESSURIZATION
 RISER DRAWINGS SHOWING THE LOCATIONS OF BAROMETRIC
 RELIEF DAMPS AND HOISTWAY VENTS.
  
 7) CONCERNING SECTION 513.11.1 LISTED ABOVE, PLEASE
 SHOW THE LOCATION OF THE GENERATOR TRANSFER SWITCHES.
  
 8) SHEET M-106: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD, FIRE SUPPRESSION SYSTEM, AND WALK IN
 COOLER AND FREEZER, HOWEVER AN AIR BALANCE CALCULATION
 IS REQUIRED PER SECTION 508.1.2:
 508.1.2AIR BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION.
  
 9) M-106: AS STATED IN THE PREVIOUS COMMENT, A SEPARATE
 PERMIT IS REQUIRED FOR THE KITCHEN HOOD AND EXHAUST
 SYSTEM, HOWEVER IT IS IMPORTANT TO NOTE AT THIS TIME OF
 THE MAIN PERMIT AND PLANS THAT COMPLIANCE WITH SECTION
 C403.2.8 FBC-17 ENERGY CONSERVATION IS REQUIRED.
 C403.2.8 KITCHEN EXHAUST SYSTEMS
 REPLACEMENT AIR INTRODUCED DIRECTLY INTO THE EXHAUST
 HOOD CAVITY SHALL NOT BE GREATER THAN 10 PERCENT OF THE
 HOOD EXHAUST AIRFLOW RATE. CONDITIONED SUPPLY AIR
 DELIVERED TO ANY SPACE SHALL NOT EXCEED THE GREATER OF
 THE FOLLOWING:
 1. THE VENTILATION RATE REQUIRED TO MEET THE SPACE
 HEATING OR COOLING LOAD.
 2. THE HOOD EXHAUST FLOW MINUS THE AVAILABLE TRANSFER
 AIR FROM ADJACENT SPACE WHERE AVAILABLE TRANSFER AIR IS
 CONSIDERED THAT PORTION OF OUTDOOR VENTILATION AIR NOT
 REQUIRED TO SATISFY OTHER EXHAUST NEEDS, SUCH AS
 RESTROOMS, AND NOT REQUIRED TO MAINTAIN PRESSURIZATION
 OF ADJACENT SPACES.
 WHERE TOTAL KITCHEN HOOD EXHAUST AIRFLOW RATE IS
 GREATER THAN 5,000 CFM (2360 L/S), EACH HOOD SHALL BE A
 FACTORY BUILT COMMERCIAL EXHAUST HOOD LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY IN COMPLIANCE
 WITH UL 710. EACH HOOD SHALL HAVE A MAXIMUM EXHAUST
 RATE AS SPECIFIED IN TABLE C403.2.8 AND SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1. NOT LESS THAN 50 PERCENT OF ALL REPLACEMENT AIR
 SHALL BE TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
 2. DEMAND VENTILATION SYSTEMS ON NOT LESS THAN 75
 PERCENT OF THE EXHAUST AIR THAT ARE CAPABLE OF NOT LESS
 THAN A 50-PERCENT REDUCTION IN EXHAUST AND REPLACEMENT
 AIR SYSTEM AIRFLOW RATES, INCLUDING CONTROLS NECESSARY
 TO MODULATE AIRFLOW IN RESPONSE TO APPLIANCE OPERATION
 AND TO MAINTAIN FULL CAPTURE AND CONTAINMENT OF SMOKE,
 EFFLUENT AND COMBUSTION PRODUCTS DURING COOKING AND
 IDLE.
 3. LISTED ENERGY RECOVERY DEVICES WITH A SENSIBLE HEAT
 RECOVERY EFFECTIVENESS OF NOT LESS THAN 40 PERCENT ON
 NOT LESS THAN 50 PERCENT OF THE TOTAL EXHAUST AIRFLOW.
 WHERE A SINGLE HOOD, OR HOOD SECTION, IS INSTALLED OVER
 APPLIANCES WITH DIFFERENT DUTY RATINGS, THE MAXIMUM
 ALLOWABLE FLOW RATE FOR THE HOOD OR HOOD SECTION SHALL
 BE BASED ON THE REQUIREMENTS FOR THE HIGHEST APPLIANCE
 DUTY RATING UNDER THE HOOD OR HOOD SECTION.
 EXCEPTION: WHERE NOT LESS THAN 75 PERCENT OF ALL THE
 REPLACEMENT AIR IS TRANSFER AIR THAT WOULD OTHERWISE BE
 EXHAUSTED.
  
 10) M-101: VERIFY THAT EXHAUST HOOD GREASE DUCT IS NOT
 TERMINATING ABOVE A WALKWAY OR ANYPLACE THAT COULD
 CREATE A PUBLIC NUISANCE OR FIRE HAZARD- SECTION
 506.3.13.2. PROVIDE THE HEIGHT OF THE OUTLET ABOVE THE
 ADJOINING GRADE.
  
 11) M-101: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY TRUNKS OF WSHP-1-1 AND WSHP-1-4 PER SECTION
 606.2.1. PLEASE NOTE AN EXEMPTION CAN BE APPLIED TO 1-4
 IF MANUFACTURER'S SPECIFICATIONS INDICATE THE SYSTEM IS
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 12) M-101 & M-102: THE OUTSIDE AIR DUCT DOES NOT APPEAR
 TO BE MAKING DIRECT CONNECTIONS TO WSHP-1-5, 1-6, AND
 1-7- PLEASE CLARIFY.
  
 13) M-101: PLEASE CLARIFY HOW SUPPLY AIR TO THE LOBBY,
 MARKET PLACE, RECEPTION AREAS ETC. IS BEING RETURNED TO
 WSHP-1-3- SECTION 601.6.
  
 14) M-101: PROVIDE DRYER EXHAUST PLANS AND DETAILS PER
 SECTION 504, AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYERS REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
  
 15) M-101: THE LAUNDRY SERVICE ROOM IS MISLABELED AS
 THE CHEF'S OFFICE.
  
 16) M-101: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL
 GAS-FIRED KITCHEN COOKING APPLIANCES AND SUBMIT
 EQUIPMENT CUT SHEETS REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD- SECTIONS 304 AND 623.1 FBC-17 FUEL
 GAS. PLEASE NOTE THERE DOES NOT APPEAR TO BE FOOD
 SERVICE PLANS INCLUDED IN THE SETS- PLEASE PROVIDE
 THEM.
  
 17) M-102: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY TRUNK OF WSHP-2-2 PER SECTION 606.2.1.
  
 18) M-102: FIRE DAMPERS NOT SHOWN AT A) THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS. B) THE S/A DUCT PENETRATION THROUGH THE
 FIRE-RATED WALL AT ROOM 226/227. C) THE 8" E/A DUCT
 PENETRATION THROUGH THE FIRE-RATED 227/231 WALL-
 SECTION 607.5.2 & 607.5.3
  
 19) M-102: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 20) M-102: SHOW HOW SUPPLY AIR FROM WSHP-2-2 AND
 WSHP-C-2 IS BEING RETURNED INTO THE MECHANICAL ROOM-
 SECTION 601.6.
  
 21) M-103: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-3
 PENETRATING THE FIRE-RATED 323/324/325 WALLS.- SECTION
 607.5.2 & 607.5.3
  
 22) M-103: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 23) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-3 IS BEING
 RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6.
  
 24) M-104: FIRE DAMPERS NOT SHOWN AT THE O/A AND E/A
 DUCTS PENETRATIONS THROUGH THE FIRE-RATED GUEST ROOM
 WALLS, AND THE SUPPLY AIR DUCTS FROM WSHP-C-10
 PENETRATING THE FIRE-RATED 1023/1025 WALLS- SECTION
 607.5.2 & 607.5.3
  
 25) M-103: INDICATE HOW ACCESS FOR SERVICE AND
 REPLACEMENT OF THE HEAT PUMPS LOCATED ABOVE DRYWALL
 CEILINGS WILL BE PROVIDED- SECTION 306.
  
 26) M-103: SHOW HOW SUPPLY AIR FROM WSHP-C-10 IS BEING
 RETURNED INTO THE MECHANICAL ROOM- SECTION 601.6.
  
 27) M-401: PROVIDE AN ENLARGED PLAN OF THE GENERATOR
 THAT PROVIDES DETAILS FOR THE ENGINE AND RADIATOR
 EXHAUST SYSTEMS, AND THE ROOM VENTILATION. CLARIFY IF
 THE GENERATOR HAS A BELLY TANK FOR DIESEL FUEL OR IF
 THERE IS TO BE A SEPARATE TANK AND TANK ROOM PROVIDED.
 SUBMIT MANUFACTURER'S SPECIFICATIONS REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
  
 28) M-501: PROVIDE WSHP INSTALLATION DETAILS.
  
 29) M-502: THE RTU ATTACHMENT DETAIL TO THE CURB IS FOR
 A CARRIER UNIT, HOWEVER THE SYSTEMS SELECTED ARE TRANE-
 PLEASE CORRECT.
  
 30) M-601: PLEASE PROVIDE COMPLETE WINDLOAD ENGINEERING
 FOR INSTALLATION OF THE OAU'S, THE ROOF AND WALL FANS,
 THE ROOFTOP DUCTWORK, AND THE WATER PIPING. PLEASE
 INCLUDE THE WIND LOAD DESIGN CRITERIA AND DETAILS FOR
 ATTACHING THE CURBS AND BRACKETS TO THE ROOF STRUCTURE,
 AND THE UNITS TO THE CURBS AND BRACKETS- SECTION
 301.15.
  
 31) PROVIDE A CONDENSATE DISPOSAL PLAN AND RISER
 DRAWING- SECTION 307.
  
 32) PROVIDE FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR ALL EXTERIOR EXHAUST AND O/A INLET LOUVERS,
 AC STANDS AND WALL BRACKETS, DUCT AND PIPE STANDS AND
 BRACKETS- RULE 9N-03 FAC.
  
 32) REQUIRED SUBMITTALS TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD: PRODUCT APPROVALS AND NOA?S,
 SMOKE CONTROL FANS, FIRE AND FIRE/SMOKE DAMPERS,
 MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, BOILER AND
 WATER HEATERS, COOKING APPLIANCES, PLENUM RATED ACCESS
 PANELS FOR ABOVE CEILING HEAT PUMPS AND FANS,
 GENERATOR, FIRE CAULKING AND FIRE WRAPPING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER