2018-02-15 16:22:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18020254
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: STRATICON LLC
 TEL: 772-210-0200 STRATICON
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. FEB. 14/ 2018
 ACTION: DENIED
  
 1) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 PLEASE UPDATE FILES SINCE THEIR MAYBE ADDITIONAL
 PERSONNEL TO ACT AS THE JOBSITE INSPECTOR.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 1A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 1C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 1D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 1E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 1F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE
 E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED,
 THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED
 AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS,
 TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK
 & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 1G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 1H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 1I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
  
  
  
 2) SHEET 042-LS-111 & 045-A-111:
  
 2A) THE LIFE SAFETY PLAN SHOWS THE EGRESS DOOR
 CAPACITIES AT 36 INCHES/ .2 = 180 OCCUPANT LOAD. PLEASE
 REDUCE ALL OPENINGS BY 2 INCHES FOR THE CLEAR WIDTH OF
 THE DOOR WHEN OPEN 90 DEGREES TO THE DOOR JAMB.
 2017 FBC-B 1010.1.1 SIZE OF DOORS. THE REQUIRED
 CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR
 THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM
 CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES. PLEASE CORRECT ALL DOORWAYS ON ALL FLOORS.
  
 2B) IN THE LIFE SAFETY PLAN ONLY DISTANCES ARE GIVEN
 FOR THE MEANS OF EGRESS. SOME OF THE AREAS SHOW THE
 OCCUPANT LOAD #1 ASSEMBLY DINING 116 TOTAL OCC. LOAD.
 IS THE KITCHEN LOAD FIGURED IN THIS CALCULATION?
 THE SAME WITH THE EMPLOYEES BREAK ROOM, LAUNDRY AND OR
 EMPLOYEES WORK AREA. WHERE THE PLAN SETS A POINT AS THE
 START OF A MEANS OF EGRESS THE PLANS SHOULD SHOW AN
 OCCUPANT LOAD AND ALONG THE PATH OF TRAVEL THE AMOUNT
 OF OCCUPANTS BEING ADDED AND THE NEW SUBTOTAL. IN THIS
 WAY THE OCCUPANT LOAD IS KNOWN FOR EACH DOOR, RAMP OR
 STAIR.
 2017 FBC-B 1003.6 MEANS OF EGRESS CONTINUITY.
  
 THE PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL
 NOT BE INTERRUPTED BY A BUILDING ELEMENT OTHER THAN A
 MEANS OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF A MEANS OF
 EGRESS SYSTEM SHALL NOT BE DIMINISHED ALONG THE PATH OF
 EGRESS TRAVEL.
  
 2C) THE LIFE SAFETY PLAN SHOWS THE 2 VERTICAL EXITS AS
 2 HOUR RATED BUT THE EXIT CORRIDOR 119 & 120 ARE SHOWN
 AS A 1 HOUR FIRE RATED CORRIDOR. PLEASE NOTE THESE
 CORRIDORS ARE IDENTIFIED WRONG, THEY ARE EXIT
 PASSAGEWAYS.
 2017 FBC-B PLEASE REFER TO 1024 .3. 1024.3
 CONSTRUCTION. EXIT PASSAGEWAY ENCLOSURES SHALL HAVE
 WALLS, FLOORS AND CEILINGS OF NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING, AND NOT LESS THAN THAT REQUIRED
 FOR ANY CONNECTING INTERIOR EXIT STAIRWAY OR RAMP ( 2
 HOUR STAIR ENCLOSURE/ 2 HOUR EXIT PASSAGEWAY). EXIT
 PASSAGEWAYS SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 PLEASE UPDATE ALL WALL IDENTIFICATION TAGS, F1 RATED
 WALLS TO F2, D RATED WALLS SHOWING NO RATING, INCLUDING
 THE 2 HOUR RATED STAIR ENCLOSURES AND IN THE DRY
 STORAGE ROOM 114 A NON-RATED WALL C WHICH GOES THROUGH
 A RATED WALL.
  
 2D) SHEET A-111 IN THE EXIT PASSAGEWAY 119 & 120.
 PLEASE NOTE UNDER THE 2017 FLORIDA BUILDING CODE
 EXISTING BUILDING CODE TABLE 1012.4 MEANS OF EGRESS
 HAZARD CATEGORIES THIS BUILDING WAS A BUSINESS
 OCCUPANCY. UNDER THE CHANGE OF OCCUPANCY TO A R1 THIS
 IS A HIGH RELATIVE HAZARD UNDER TABLE 1012.4.
 EXIST. BUILD. CODE 1012.4.1 MEANS OF EGRESS FOR CHANGE
 TO HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO A HIGHER HAZARD CATEGORY
 (LOWER NUMBER) AS SHOWN IN TABLE 1012.4, THE MEANS OF
 EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10
 OF THE FLORIDA BUILDING CODE, BUILDING. THE 2017 FBC-B
 STATES IN 1024.1 EXIT PASSAGEWAYS. AN EXIT PASSAGEWAY
 SHALL NOT BE USED FOR ANY PURPOSE OTHER THAN AS A MEANS
 OF EGRESS AND A CIRCULATION PATH. THE 2012 IBC CODE
 COMMENTARY STATES THE ONLY OPENINGS THAT ARE PERMITTED
 IN THE FIRE RESISTANCE RATED EXIT PASSAGEWAY ARE DOORS
 THAT LEAD EITHER FROM NORMALLY OCCUPIED SPACES, FROM
 THE ENCLOSURE FOR THE EXIT STAIRWAY AND DOORS LEADING
 TO THE OUTSIDE.
  
 PLEASE ALSO REVIEW SECTION 1023 2017 FBC-B INTERIOR
 EXIT & STAIRWAYS& RAMPS, 1023.11 TERMINATION AND
 EXTENSIONS. EXCEPTION 1 ALLOWS FOR OPENINGS IN THE EXIT
 PASSAGEWAY SERVING A SMOKEPROOF ENCLOSURE ARE PERMITTED
 WHERE THE EXIT PASSAGEWAY IS PROTECTED AND PRESSURIZED
 IN THE SAME MANNER AS THE SMOKEPROOF ENCLOSURE, AND
 OPENINGS ARE PROTECTED AS REQUIRED FOR ACCESS FROM
 OTHER FLOORS.
  
 PLEASE ALSO REVIEW SECTION 1024.7 VENTILATION FOR EXIT
 PASSAGEWAYS PROVIDE WHICH OF THE 3 METHODS WILL
 INSTALLED.
  
 2E) PLEASE ALSO REVIEW IN THE 2 HOUR FIRE RATED EXIT
 PASSAGEWAY 119 DOOR 116 AND SIDELIGHT, IN THE 2017
 FBC-B TABLE 716.5 FOR A 2 HOUR WALL ONLY ALLOWS A 100
 SQ. IN. VISION PANEL IN THE DOOR AND SIDELIGHT OR
 TRANSOM NOT PERMITTED.
  
 2F) PLEASE NOTE WITH BOTH EXIT PASSAGE WAYS 119 & 120
 THE ONLY ALLOWABLE PENETRATIONS ARE THOUGH ALLOWED
 UNDER SECTION FBC-B 1024.6 PENETRATIONS INTO OR THROUGH
 AN EXIT PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY
 SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL
 BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2G) PLEASE REVIEW SHEET M-101 AND THE DUCTWORK THAT IS
 RUNNING THROUGH THE EXIT PASSAGEWAY. SHOW HOW
 COMPLIANCE WITH SECTION FBC-B 1024.7 IS TO BE ACHIEVED.
 1024.7 VENTILATION.
 EQUIPMENT AND DUCTWORK FOR EXIT PASSAGEWAY VENTILATION
 AS PERMITTED BY SECTION 1024.6 SHALL COMPLY WITH ONE OF
 THE FOLLOWING:
 1. THE EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR
 TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE
 EXIT PASSAGEWAY BY DUCTWORK ENCLOSED IN CONSTRUCTION AS
 REQUIRED FOR SHAFTS.
 2. WHERE THE EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT PASSAGEWAY, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR THE AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED FOR SHAFTS. 2017 FLORIDA BUILDING CODE W 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 105.1.1. PERMIT
 REQUIRED.
 3. WHERE LOCATED WITHIN THE BUILDING, THE EQUIPMENT AND
 DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH
 CONSTRUCTION AS REQUIRED FOR SHAFTS.
 IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR
 SHAFT ENCLOSURES.
 EXIT PASSAGEWAY VENTILATION SYSTEMS SHALL BE
 INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS.
  
 2H) PLEASE NOTE AS MEASURED FOR THE EXITS AND
 REMOTENESS, SPRINKLERED BUILDING 1/3 RD. THE OVERALL
 DISTANCE CENTER OF DOOR LINE TO CENTER OF DOOR LINE.
 2017 FBC-B 1007.1.1 EXCEPTION 1 & 2.
  
 1ST FLOOR SHEET 047-A-112 THE OVERALL DIAGONAL DISTANCE
 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 133
 THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT
 DOOR 135 IS 42 FT. DOES NOT MEET REMOTENESS.
  
 2ND FLOOR SHEET 051-A-122 THE OVERALL DIAGONAL DISTANCE
 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT DOOR 233
 THROUGH CENTERLINE OF RATED CORRIDOR TO CENTERLINE EXIT
 DOOR 235 IS 42 FT. DOES NOT MEET
 REMOTENESS.
  
 3RD-9TH FLOORS SHEET 054-A-1.32 THE OVERALL DIAGONAL
 DISTANCE 143 FT. /3= 47.66 FT. DISTANCE CENTERLINE EXIT
 DOOR 333 THROUGH CENTERLINE OF RATED CORRIDOR TO
 CENTERLINE EXIT DOOR 335 IS 48.16 FT. DOES MEET
 REMOTENESS TEST.
  
 2I) SHEET P-106 THE EXIT PASSAGE WAY LISTED ON THE
 ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS
 LISTED HERE AS EXIT CORRIDOR 121. PLEASE REMOVE ALL ?
 INCH, 3 INCH AND 4 INCH COLD WATER AS WELL AS 1 ? INCH
 HOT WATER PIPING FROM THE 2 HOUR FIRE RATED EXIT
 PASSAGEWAY. SEE FBC-B SECTION 1024.6 PENETRATIONS.
  
 PENETRATIONS INTO OR THROUGH AN EXIT PASSAGEWAY ARE
 PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION AND ELECTRICAL RACEWAY SERVING THE EXIT
 PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL
 NOT BE PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2J) SHEET E-106 THE EXIT PASSAGE WAY LISTED ON THE
 ARCHITECTURAL AND MECHANICAL SHEETS AS 119 AND 120 IS
 LISTED HERE AS EXIT CORRIDOR 121. THE SHEET INDEX LIST
 SHEET E-105 AS THE 1ST FLOOR OVERALL LIGHTING PLAN,
 THERE SEEMS TO BE A DISCREPANCY IN PLANS. IN EITHER
 CASE SHOW COMPLIANCE WITH FBC-B SECTION 1024.6
 PENETRATIONS. PENETRATIONS INTO OR THROUGH AN EXIT
 PASSAGEWAY ARE PROHIBITED EXCEPT FOR EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION AND ELECTRICAL RACEWAY
 SERVING THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL
 BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2K) LS-111 AND A-111A BOTH SHOW WITHIN THE 2 HOUR EXIT
 PASSAGE WAY 120 TAKING PART OF THE OCCUPANTS FROM THE 2
 HOUR ENCLOSURE OUT THROUGH DOOR 124 IN FRONT OF THE
 ELEVATOR LOBBY ON THE 1ST FLOOR, OUT THROUGH THE
 GENERAL LOBBY AND OUT THE FRONT DOORS. THE DOOR 124 IS
 A OUTSWING DOOR AND DIRECTLY IN FRONT
 IS DOOR 125 ALSO A OUTSWING DOOR THAT WOULD IMPEDE THE
 EXITING FROM THE VERTICAL EXIT STAIRWAY. NOTE THE DOOR
 SWING DOES NOT CUT THE REQUIRED EGRESS WIDTH IN HALF.
  
 2L) LS-111 AND A-111A PLEASE REVIEW LAUNDRY CHUTE
 SHAFT. THE LIFE SAFETY PLAN DOES NOT INDICATE THE
 LAUNDRY SHAFT AS RATED. THE A-111A SHEET SHOWS THE
 RATING ON THE LAUNDRY SHAFT WALLS AS F1 ONE HOUR FIRE
 RATED WALL UL 448, NOT EVEN SHAFT WALL CONSTRUCTION.
 SHAFT WALL CONSTRUCTION SHALL BE 2 HOURS WHEN
 CONNECTING 4 STORIES OR MORE. FBC-B 713.4. FIRE
 RESISTANCE RATING. THE PLANS WILL NEED TO BE UPDATES
 SHOWING A 2 HOUR SHAFT AND MEETING ALL OF THE
 REQUIREMENTS OF FBC-B 713.13.1-4 AND 713.13.6.
  
 2M) THE PLANS SHOW A SPACE THAT IS VOID, ENCLOSED ON
 THE KITCHEN, LAUNDRY SHAFT AND EXIT PASSAGE WAY 120,
 WHAT IS SPACE TO BE USED FOR? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2N) SHEET A-407 NOTICE ONLY!!! THE ENLARGED MENS &
 WOMENS RESTROOM ON SHEET A407 & A-408 MEASURE 7-0
 OVERALL. THE LAYOUT JUST BARELY MEETS THE REQUIREMENT
 FOR THE CLEAR FLOOR SPACE UNDER THE ACCESSIBILITY CODE
 SECTION 604.3.1. DEPENDING ON THE SIZE LAV TO BE
 INSTALLED THE CLEAR FLOOR SPACE MAY NOT BE ACHIEVED!!!
  
 2O) SHEET A-407 & A-408 THE MIRRORS IN THE VANITY
 ELEVATION ARE DIMENSIONED WITH THE DIMENSION OF 3 FOOT
 4 ? INCHES TO THE BOTTOM OF THE MIRROR FRAME. THE 2017
 FBC-ACCESSIBILITY CODE REQUIRES A MAXIMUM OF 40 INCHES
 TO THE REFLECTIVE SURFACE TO FINISH FLOOR AS A MAXIMUM
 HEIGHT. SEE 603.3.
  
 2P) SHEET A-111 EMPLOYEE RESTROOM SHOWS A ACCESSIBLE
 SHOWER. THIS PLAN DOES NOT REFERENCE ANY DETAILS FOR
 THE ACCESSIBLE SHOWER, WHEN MEASURED THE SHOWER IS 3X3
 FEET. THERE IS A SEAT WITHIN THE SHOWER BUT THE SEAT
 FALL SHORT OF COMPLYING WITH 2017 ACC. CODE 610.3.
 610.3.2 L-SHAPED SEATS.
 THE REAR EDGE OF AN L-SHAPED SEAT SHALL BE 2 1/2 INCHES
 MAXIMUM AND THE FRONT EDGE 15 INCHES MINIMUM AND 16
 INCHES MAXIMUM FROM THE SEAT WALL. PLEASE PROVIDE GRAB
 BARS FOR A TRANSFER SHOWER IN COMPLIANCE WITH 608.3.1.
  
 2Q) SHEET A-112 THE EMPLOYEE RESTROOM SHOWS A OVERALL
 DIMENSION OF THE RESTROOM BUT NOT THE CLEAR FLOOR SPACE
 REQUIRED FOR THE WATER CLOSET. SEE ACC. CODE 604.3.1.
 SIZE.
  
 2R) SHEET 042-LS-111 THE FLOOR PLAN SHOWS A DINING AND
 BAR AREA, PLEASE PROVIDE COMPLIANCE WITH THE 2017
 ACCESSIBILITY CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 2S) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2T) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
 902.1 .DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. DINING
 SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, TABLES,
 LUNCH COUNTERS, AND BOOTHS.
 2T)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2T)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2U) POOL, GENERATOR, KITCHEN HOODS, SUPPRESSION, GAS,
 FENCES, SIGNS, FIRE SPRINKLERS, FIRE ALARMS,
 LANDSCAPING, IRRIGATION PERMITS ARE NOT REVIEWED UNDER
 THE MAIN BUILDING PERMIT AND ALL REQUIRE A SEPARATE
 REVIEW AND FEE.
  
 2V) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 PLANS WERE DEVELOPED UNDER THE 2014 FBC-B BROUGHT IN
 AFTER DEC. 31/ 2017 WHICH WAS THE ADOPTION DATE OF THE
 2017 FBC-B.
  
 2W) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 PLANS WERE DEVELOPED A CONSTRUCTION TYPE II-A, THIS
 ONLY ALLOWS UNDER THE 2014 CODE TABLE 503 A 4 STORY
 BUILDING WITH ONE STORY INCREASE, IT WOULD BE REQUIED
 TO BE A CONSTRUCTION TYPE I-B . UNDER THE 2017 FBC-B
 TABLE 504.4 THE BUILDING TYPE WOULD ALSO BE REQUIRED TO
 BE I-B.
  
 2X) SHEET 005-GN-1 BUILDING CODE SUMMARY INDICATES THE
 HOTEL AS A R-2 HOTEL TRANSIENT, PLEASE NOTE R-1 IS
 CONSIDERED TRANSIENT A STAY30 DAYS OR LESS, R-2 IS
 CONSIDERED NON-TRANSIENT OR STAYS OVER 30 DAYS. SEE
 FBC-B 310.3 & 310.4.
  
 2Y) SHEETS 042-ALS-111 NOR SHEET 045-A-111-A SHOW THE
 LOCATION OF THE FIRE PUMP LOCATION. SHEET E-101 SHOWS
 THE FIRE PUMP IN THE MECHANICAL/ ELECTRICAL ROOM 127.
 PLEASE SHOW COMPLIANCE WITH:
 2017 FBC-B [F]403.3.4 FIRE PUMP ROOM. FIRE PUMPS SHALL
 BE LOCATED IN ROOMS PROTECTED IN ACCORDANCE WITH
 SECTION 913.2.1. 913.2.1 PROTECTION OF FIRE PUMP ROOMS.
 FIRE PUMPS SHALL BE LOCATED IN ROOMS THAT ARE SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING BY 2-HOUR FIRE
 BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR
 2-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1.IN OTHER THAN HIGH-RISE BUILDINGS, SEPARATION BY
 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR 1-HOUR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH, SHALL BE
 PERMITTED IN BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2.
  
 3) SHEET 046-A-111-B:
 3A) THE COVERED ENTRY PORT COCHERE SHOWS THE USE OF A
 LULA LIFT, PLEASE PROVIDE CONFIRMATION THE
 LIFT MEETS THE LIMITED-USE/LIMITED-APPLICATION
 ELEVATORS SHALL COMPLY WITH 408 AND WITH ASME A17.1
 ?REFERENCED STANDARDS?.
  
 3B) SHEET 046-A-111-B SHOWS A NEW FIRE COMMAND ROOM.
 [F]403.4 EMERGENCY SYSTEMS. THE DETECTION, ALARM AND
 EMERGENCY SYSTEMS OF HIGH-RISE BUILDINGS SHALL COMPLY
 WITH SECTIONS 403.4.1 THROUGH 403.4.8.
  
 3C) [F]403.4.1 SMOKE DETECTION. SMOKE DETECTION SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.1.
  
 3D) [F]403.4.2 FIRE ALARM SYSTEM. A FIRE ALARM SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.2.13.
  
 3E) [F]403.4.3 STANDPIPE SYSTEM. A HIGH-RISE BUILDING
 SHALL BE EQUIPPED WITH A STANDPIPE SYSTEM AS REQUIRED
 BY SECTION 905.3.
  
 3F) [F]403.4.4 EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 3G) [F]403.4.5 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 3H)SEMI-COMPLIED. [F]403.4.6 FIRE COMMAND. A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE
 PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT.
  
 3I) 403.4.7 SMOKE REMOVAL. TO FACILITATE SMOKE REMOVAL
 IN POST-FIRE SALVAGE AND OVERHAUL OPERATIONS, BUILDINGS
 AND STRUCTURES SHALL BE EQUIPPED WITH NATURAL OR
 MECHANICAL VENTILATION FOR REMOVAL OF PRODUCTS OF
 COMBUSTION IN ACCORDANCE WITH ONE OF THE FOLLOWING:
 1.EASILY IDENTIFIABLE, MANUALLY OPERABLE WINDOWS OR
 PANELS SHALL BE DISTRIBUTED AROUND THE PERIMETER OF
 EACH FLOOR AT NOT MORE THAN 50-FOOT (15 240 MM)
 INTERVALS. THE AREA OF OPERABLE WINDOWS OR PANELS SHALL
 BE NOT LESS THAN 40 SQUARE FEET (3.7 M2) PER 50 LINEAR
 FEET (15 240 MM) OF PERIMETER.
  
 EXCEPTIONS:
 1.IN GROUP R-1 OCCUPANCIES, EACH SLEEPING UNIT OR SUITE
 HAVING AN EXTERIOR WALL SHALL BE PERMITTED TO BE
 PROVIDED WITH 2 SQUARE FEET (0.19 M2) OF VENTING AREA
 IN LIEU OF THE AREA SPECIFIED IN ITEM 1.
 2.WINDOWS SHALL BE PERMITTED TO BE FIXED PROVIDED THAT
 GLAZING CAN BE CLEARED BY FIRE FIGHTERS.
 2.MECHANICAL AIR-HANDLING EQUIPMENT PROVIDING ONE
 EXHAUST AIR CHANGE EVERY 15 MINUTES FOR THE AREA
 INVOLVED. RETURN AND EXHAUST AIR SHALL BE MOVED
 DIRECTLY TO THE OUTSIDE WITHOUT RECIRCULATION TO OTHER
 PORTIONS OF THE BUILDING.
 3.ANY OTHER APPROVED DESIGN THAT WILL PRODUCE
 EQUIVALENT RESULTS.
  
 3J) [F]403.4.8 STANDBY AND EMERGENCY POWER. A STANDBY
 POWER SYSTEM COMPLYING WITH SECTION 2702 AND SECTION
 3003 SHALL BE PROVIDED FOR THE STANDBY POWER LOADS
 SPECIFIED IN SECTION 403.4.8.3. AN EMERGENCY POWER
 SYSTEM COMPLYING WITH SECTION 2702 SHALL BE PROVIDED
 FOR THE EMERGENCY POWER LOADS SPECIFIED IN SECTION
 403.4.8.4.
  
 3K) [F]403.4.8.1 EQUIPMENT ROOM. IF THE STANDBY OR
 EMERGENCY POWER SYSTEM INCLUDES A GENERATOR SET INSIDE
 A BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE BARRIERS CONSTRUCTED IN
 ACCORDANCE WITH SECTION 707 OR HORIZONTAL ASSEMBLIES
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 SYSTEM SUPERVISION WITH MANUAL START AND TRANSFER
 FEATURES SHALL BE PROVIDED AT THE FIRE COMMAND CENTER.
  
 4) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 4A) THIS STATEMENT IS GOING TO BE A COMMON STATEMENT
 FOR ALL FLOORS CONTAINING SLEEPING ROOMS. THE PLANS
 WILL NEED TO PROVIDE A MATRIX PROVIDING THE TOTAL
 AMOUNT OF SLEEPING ROOMS. IT APPEARS THERE ARE 168
 SLEEPING ROOMS. A-4.05A INDICATES THE STYLE OF ROOM FOR
 A ADA DOUBLE QUEEN AND SHEET A-406-A SHOWS THE ADA KING
 PLEASE PROVIDE A MATRIX WHICH UNITS ARE ACCESSIBLE.
 PLEASE USE TABLE 224.2 OF THE 2017 ACCESS. CODE TO
 PROVIDE THE NUMBER OF UNITS WITH ROLL-IN SHOWER, NUMBER
 OF ROOMS WITHOUT THE ROLL IN SHOWER AND TOTAL NUMBER OF
 REQUIRED ROOMS.
  
 4B) ACCESS. CODE SHOW 224.5 DISPERSION. GUEST ROOMS
 REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING WITH
 806.2 AND GUEST ROOMS REQUIRED TO PROVIDE COMMUNICATION
 FEATURES COMPLYING WITH 806.3 SHALL BE DISPERSED AMONG
 THE VARIOUS CLASSES OF GUEST ROOMS, AND SHALL PROVIDE
 CHOICES OF TYPES OF GUEST ROOMS, NUMBER OF BEDS, AND
 OTHER AMENITIES COMPARABLE TO THE CHOICES PROVIDED TO
 OTHER GUESTS. WHERE THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO COMPLY WITH 806 IS NOT SUFFICIENT TO ALLOW
 FOR COMPLETE DISPERSION, GUEST ROOMS SHALL BE DISPERSED
 IN THE FOLLOWING PRIORITY: GUEST ROOM TYPE, NUMBER OF
 BEDS, AND AMENITIES. AT LEAST ONE GUEST ROOM REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 ALSO PROVIDE COMMUNICATION FEATURES COMPLYING WITH
 806.3. NOT MORE THAN 10 PERCENT OF GUEST ROOMS REQUIRED
 TO PROVIDE MOBILITY FEATURES COMPLYING WITH 806.2 SHALL
 BE USED TO SATISFY THE MINIMUM NUMBER OF GUEST ROOMS
 REQUIRED TO PROVIDE COMMUNICATION FEATURES COMPLYING
 WITH 806.3.
  
 4C) ACCESS. CODE SHOW COMPLIANCE WITH: 224.1.2 GUEST
 ROOM DOORS AND DOORWAYS. ENTRANCES, DOORS, AND DOORWAYS
 PROVIDING USER PASSAGE INTO AND WITHIN GUEST ROOMS THAT
 ARE NOT REQUIRED TO PROVIDE MOBILITY FEATURES COMPLYING
 WITH 806.2 SHALL COMPLY WITH 404.2.3.
  
 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL PROVIDE A
 CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM. CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
  
 806.2.3 SLEEPING AREAS. AT LEAST ONE SLEEPING AREA
 SHALL PROVIDE A CLEAR FLOOR SPACE COMPLYING WITH 305 ON
 BOTH SIDES OF A BED. THE CLEAR FLOOR SPACE SHALL BE
 POSITIONED FOR PARALLEL APPROACH TO THE SIDE OF THE
 BED. EXCEPTION: WHERE A SINGLE CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR PARALLEL APPROACH IS
 PROVIDED BETWEEN TWO BEDS, A CLEAR FLOOR OR GROUND
 SPACE SHALL NOT BE REQUIRED ON BOTH SIDES OF A BED.
  
  
 806.2.4 TOILET AND BATHING FACILITIES. AT LEAST ONE
 BATHROOM THAT IS PROVIDED AS PART OF A GUEST ROOM SHALL
 COMPLY WITH 603. NO LESS THAN ONE WATER CLOSET, ONE
 LAVATORY, AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH
 APPLICABLE REQUIREMENTS OF 603 THROUGH 610. IN
 ADDITION, REQUIRED ROLL-IN SHOWER COMPARTMENTS SHALL
 COMPLY WITH 608.2.2 OR 608.2.3. TOILET AND BATHING
 FIXTURES REQUIRED TO COMPLY WITH 603 THROUGH 610 SHALL
 BE PERMITTED TO BE LOCATED IN MORE THAN ONE TOILET OR
 BATHING AREA, PROVIDED THAT TRAVEL BETWEEN FIXTURES
 DOES NOT REQUIRE TRAVEL BETWEEN OTHER PARTS OF THE
 GUEST ROOM.
  
  
 806.2.4.1 VANITY COUNTER TOP SPACE. IF VANITY COUNTER
 TOP SPACE IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR
 BATHING ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN
 TERMS OF SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO
 BE PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING
 ROOMS.
 ADVISORY 806.2.4.1 VANITY COUNTER TOP SPACE. THIS
 PROVISION IS INTENDED TO ENSURE THAT ACCESSIBLE GUEST
 ROOMS ARE PROVIDED WITH COMPARABLE VANITY COUNTER TOP
 SPACE.
  
 4D) PLEASE PROVIDE COMPLIANCE WITH ACCESS. CODE TABLE
 224.4 GUEST ROOMS WITH COMMUNICATION FEATURES, PROVIDE
 ALSO IN MATRIX SHOWING WHAT ROOMS ARE TO COMPLY.
  
 5) THE 2ND FLOOR LEVEL, SHEETS 043-LS-121, 050-A-121 &
 051-A-122:
 5A) SHEET 043-LS-121 IS MISSING THE ROOM LABEL 224 AND
 IDENTIFIED AS A WARMING KITCHEN. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. NOTE, CANNOT EXIT THROUGH A
 KITCHEN OR STORAGE ROOM. ALSO SEE 2017 FBC-B 1016.2(2)
 (5) EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS, OR SPACES USED FOR SIMILAR PURPOSES.
  
 5B) MEETING ROOM 226, YOUR OVERALL DIAGONAL FOR THIS
 ROOM IS 50.50 FT. 1/3RD THE OVERALL DISTANCE IS 16 FOOT
 10 INCHES. THE 2 EXIT DOORS MEET THIS REQUIREMENT BUT
 THE 2 MEANS OF ACCESS CONVERGE BETWEEN THE DOOR LEADING
 TO STAIR 233 AND DOOR 205. BETWEEN THE WALL OF THE
 STAIR AND DOOR 205 THERE IS ONLY 12 FEET OR THE 2 EXITS
 CONVERGE, DOES NOT MEET THE REQUIREMENT OF REMOTENESS
 UNDER 2017 FBC-B 1007.1.1EXCEP. 2. 1/3 DISTANCE APART.
  
 5C) SHEET 050-A-121 THE COMMON WALL BETWEEN THE MEETING
 ROOM STORAGE CLOSET AND GUEST ROOM 222 IS IDENTIFIED
 WITH WALL TAG F3. PLEASE NOTE THE WALL SCH. ON A-501
 DOES NOT ASSIGN A STC RATING TO THIS WALL.
 FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5D) PAGE 051-A-122 & LS-1.21. GUEST ROOM 220 THIS
 COMMENT IS TO STAND FOR ALL FLOORS 2-10. THE COMMON
 PATH OF TRAVEL IS TAKEN FROM THE DOORWAY OR THE
 BEGINNING OF THE EXIT ACCESS CORRIDOR. PLEASE NOTE
 COMMON PATH OF EGRESS TRAVEL,
 DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL
 DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE
 AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW
 THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE
 POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT
 FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS
 THE TRAVEL DISTANCE EXCEEDS 75 FEET.
  
 5E) SHEET 050-A-121. COMMON COMMENT FOR ALL FLOORS
 2-10. THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND
 IDENTIFIED WITH A WALL TAG F2. THIS WALL IS A 1 HOUR
 RATING REQUIRES A 2 HOUR FIRE RATING PER 713.4
 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE.
  
 5F) SHEET 050-A-121 COMMON COMMENT FOR ALL FLOORS 2-10.
 THE LINEN CHUTE SHOWS THE SHAFT WALLS AROUND IDENTIFIED
 WITH A WALL TAG F2. PLEASE ALSO PROVIDE THE CORRECT UL
 LISTING FOR SHAFT WALL CONSTRUCTION. 713.4
 FIRE-RESISTANCE RATING.
  
 6) SHEET 054-A-132 GUEST ROOMS 302, THIS COMMENT WILL
 STAND FOR THIS ROOM ALL FLOORS 3-9. THE COMMON PATH OF
 TRAVEL IS TAKEN FROM THE DOORWAY OR THE BEGINNING OF
 THE EXIT ACCESS CORRIDOR. PLEASE NOTE COMMON PATH OF
 EGRESS TRAVEL,
 DEFINITION: THAT PORTION OF THE EXIT ACCESS TRAVEL
 DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE
 AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 PLEASE PROVIDE THE COMMON PATH OF EGRESS TRAVEL SHOW
 THE COMMON PATH OF EGRESS TRAVEL FROM THE MOST REMOTE
 POINT IN THE ROOM AND AROUND FURNITURE AND ONE FOOT
 FROM WALL LINES TO THE CLOSET VERTICAL EXIT. IT APPEARS
 THE TRAVEL DISTANCE EXCEEDS 75 FEET.
  
 7) SHEET 067-A-305:
 7A) DETAIL 2 EXTERIOR STAIR. THE PLAN INDICATES THE
 RISE OF 7 INCHES AND RUN OF 11 INCHES BUT DOES NOT
 PROVIDE THE CIRCULAR AREA MADE OF THE RISE, RUN AND
 SLOPE OF THE BOTTOM GUARDRAIL. SHOW COMPLIANCE WITH
 2017 FBC-B 1015.4 EXCEPTION 2. 2. THE TRIANGULAR
 OPENINGS AT THE OPEN SIDES OF A STAIR, FORMED BY THE
 RISER, TREAD AND BOTTOM RAIL SHALL NOT ALLOW PASSAGE OF
 A SPHERE 6 INCHES (152 MM) IN DIAMETER.
  
 7B) DETAIL 2 EXTERIOR STAIR. THE UPPER LANDING SHOWS
 THE GUARDRAIL AT 3 FOOT 6 INCHES OF 43 INCHES.
 THE GUARDRAIL DROPS VERTICALLY 4 INCHES AT THE FIRST
 RISER. THE HEIGHT MEASUREMENT FOR THE GUARDRAIL IS TO
 BE TAKEN AT THE NOSING OF THE RISER, VERTICALLY. SEE
 2017 FBC-B 1015.3 HEIGHT. REQUIRED GUARDS SHALL BE NOT
 LESS THAN 42 INCHES (1067 MM) HIGH, MEASURED
 VERTICALLY.
  
 7C) THE BOTTOM OF THE GUARDRAIL DOES NOT CONTINUE DOWN
 THE SLOPE 11 INCHES PAST THE LAST RISER, THIS IS WHERE
 THE HORIZONTAL EXTENSION WOULD BEGIN, THAT IS ALSO THE
 REASON ON THE STAIRS THE HANDRAIL IS 34 INCHES IN
 HEIGHT, THE HANDRAIL ALSO DOES NOT CONTINUE 11 INCHES
 PAST THE LAST RISER BEFORE CONTINUING THE HORIZONTAL
 EXTENSION. 2017 FBC-B 1014.6 HANDRAIL EXTENSIONS. THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 8) SHEET A104-A-601 DOOR STYLE 20 IS A SLIDING BARN
 DOOR AND TRACK SYSTEM, HARDWARE GROUP 11 INDICATES ADA
 COMPLIANT PULLS. THE DOOR HAS TO MAINTAIN A 32 INCH
 CLEAR OPENING AS WELL AS THE HARDWARE MEET COMPLIANCE
 WITH :
 2017 ACCESS. CODE 404.2.7 DOOR AND GATE HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE
 PARTS ON DOORS AND GATES SHALL COMPLY WITH 309.4.
 OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES
 MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN
 POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND
 USABLE FROM BOTH SIDES.
  
 9) WITH NOT KNOWING THE LOCATION OF THE ACCESSIBLE
 ROOMS, THIS IS ONE OF THE CONCERNS WITH THE EGRESS DOOR
 TO THE INDUVIAL SUITES. THIS EXAMPLE IS FOR ALL ROOMS,
 THE ADA ROOM NEED TO COMPLY. SEE ROOM COLUMN 214 -1013.
 THE ENTRY DOOR IS RECESSED BACK 10 INCHES FROM THE
 REMAINDER OF THE CORRIDOR WALL.
 SHOW COMPLIANCE WITH THE 2017 FLORIDA ACCESSIBILITY
 CODE FOR THE ACCESSIBLE ROOMS. 404.2.4.3 RECESSED DOORS
 AND GATES. MANEUVERING CLEARANCES FOR FORWARD APPROACH
 SHALL BE PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES
 (455 MM) OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE
 THAN 8 INCHES (205 MM) BEYOND THE FACE OF THE DOOR,
 MEASURED PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
  
 10) WINDOWS ARE UNDER A SEPARATE PERMITS BUT THERE WILL
 BE OTHER COMPONENTS AND CLADDING REQUIREMENTS. 2017
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER