2018-02-14 10:00:24TEMPORARY STRUCTURES
  
 LESS THAN 180 DAYS
 GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS
  
 1. PROVIDE LIFE SAFETY PLAN IF SIDES ARE CLOSED
 A. SITE PLAN ? LOCATION PER FBC SEC. 602
 B. MEANS OF EGRESS ? PER FBC CHPT. 10
 TRAVEL DISTANCE 100 FT. OR LESS TO ANY EXIT
 C. OCCUPANCY LOAD ? PER FBC TABLE 1004.1.2
  
 2. PROVIDE STATEMENT FOR DATE OF ASSEMBLY AND DATE OF
 REMOVAL.
  
 3. APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO (2)
 WEEKS PRIOR TO EVENT
  
 4. 3103.1.1 CONFORMANCE.
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
  