2018-02-14 16:32:01 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- PROPOSED INSTALLATION STILL IS NOT CLEAR. THERE ARE |
| FOUR DIFFERENT MOUNTING CONDITIONS SHOWN (A, B, E AND |
| J). IT IS NOT CLEAR HOW THE FOUR MOUNTING CONDITIONS |
| ARE GOING TO BE MET IF THE 3 WINDOWS ARE LOCATED IN THE |
| SAME WALL PLANE. IN ADDITION, CLARIFY WHY ONLY WINDOW |
| #3 HAS A DIFFERENT CONNECTION TYPE AT THE BOTTOM. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 2- INSTALLATION SCHEDULE SPECIFIES CONCRETE AS THE |
| SUBSTRATE WHERE THE STORM PANELS ARE GOING TO BE |
| INSTALLED. ACCORDING TO CITY RECORDS. THESE ARE ARCHED |
| WINDOWS. THERE IS WOOD FRAME AROUND TOP OF WINDOW. THIS |
| IS NOT CONCRETE SUBSTRATE. CLARIFY IF PANELS ARE GOING |
| TO BE INSTALLED AT THE PRECAST LINTEL OR AT THE WOOD |
| FRAMED AREA. BOTTOM OF WINDOW IS CONCRETE BLOCK. REVISE |
| SUBSTRATE INFORMATION SHOWN ON THE INSTALLATION |
| SCHEDULE. AND, REVISE ANCHOR TYPE AND SPACING |
| ACCORDINGLY. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- EDGE DISTANCE NEED TO TAKE INTO CONSIDERATION THE |
| THICKNESS OF THE STUCCO OR WALL FINISH. REVISE EDGE |
| DISTANCE ON THE INSTALLATION SCHEDULE AS REQUIRED. |
| SEC.107.2.1 CITY AMENDMENTS. |
| |
| |