2018-02-14 16:32:01RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- PROPOSED INSTALLATION STILL IS NOT CLEAR. THERE ARE
 FOUR DIFFERENT MOUNTING CONDITIONS SHOWN (A, B, E AND
 J). IT IS NOT CLEAR HOW THE FOUR MOUNTING CONDITIONS
 ARE GOING TO BE MET IF THE 3 WINDOWS ARE LOCATED IN THE
 SAME WALL PLANE. IN ADDITION, CLARIFY WHY ONLY WINDOW
 #3 HAS A DIFFERENT CONNECTION TYPE AT THE BOTTOM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- INSTALLATION SCHEDULE SPECIFIES CONCRETE AS THE
 SUBSTRATE WHERE THE STORM PANELS ARE GOING TO BE
 INSTALLED. ACCORDING TO CITY RECORDS. THESE ARE ARCHED
 WINDOWS. THERE IS WOOD FRAME AROUND TOP OF WINDOW. THIS
 IS NOT CONCRETE SUBSTRATE. CLARIFY IF PANELS ARE GOING
 TO BE INSTALLED AT THE PRECAST LINTEL OR AT THE WOOD
 FRAMED AREA. BOTTOM OF WINDOW IS CONCRETE BLOCK. REVISE
 SUBSTRATE INFORMATION SHOWN ON THE INSTALLATION
 SCHEDULE. AND, REVISE ANCHOR TYPE AND SPACING
 ACCORDINGLY. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- EDGE DISTANCE NEED TO TAKE INTO CONSIDERATION THE
 THICKNESS OF THE STUCCO OR WALL FINISH. REVISE EDGE
 DISTANCE ON THE INSTALLATION SCHEDULE AS REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
  