Plan Review Notes
Plan Review Notes For Permit 18020198
Permit Number 18020198
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-14 13:08:221ST REVIEW: FBC 2014 5TH EDITION
 GAS COMMENTS:
 1. IF NO MANUFACTURE SPECIFICATION WITH BTU LOAD IS
 AVAILABLE THAN THE BTU LOAD FOR THE APPLIANCE OUT OF
 TABLE 402.2 SHALL BE USED FOR SIZING THE SYSTEM. PER
 FBC FG 402.2
 2. PER FBC FG TABLE 40202 THE DRYER SHALL BE LISTED AT
 35,000 BTU AND THE COOK TOP WILL BE 40,000 WITH A TOTAL
 OF 75,000 WHICH IS OVER THE MAX BTU FOR ? CSST @ 70?
 3. PLEASE LIST THE CODE THE SYSTEM IS DESIGNED UNDER IT
 SHALL BE FBCFG 2014 5TH EDITION
 4. THE ORIGINAL GAS PLAN WAS DESIGNED BY LIC ENGINEER
 ANY REVISIONS SHALL BE SIGNED AND SEALED BY DESIGNER OF
 RECORD. PER FAC 61G15-23.003
 5. PROVIDE COMBUSTION AIR CALCULATIONS. PER FBC FG 304
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  