Plan Review Notes For Permit 18020198 |
Permit Number |
18020198 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-14 13:08:22 | 1ST REVIEW: FBC 2014 5TH EDITION | | GAS COMMENTS: | | 1. IF NO MANUFACTURE SPECIFICATION WITH BTU LOAD IS | | AVAILABLE THAN THE BTU LOAD FOR THE APPLIANCE OUT OF | | TABLE 402.2 SHALL BE USED FOR SIZING THE SYSTEM. PER | | FBC FG 402.2 | | 2. PER FBC FG TABLE 40202 THE DRYER SHALL BE LISTED AT | | 35,000 BTU AND THE COOK TOP WILL BE 40,000 WITH A TOTAL | | OF 75,000 WHICH IS OVER THE MAX BTU FOR ? CSST @ 70? | | 3. PLEASE LIST THE CODE THE SYSTEM IS DESIGNED UNDER IT | | SHALL BE FBCFG 2014 5TH EDITION | | 4. THE ORIGINAL GAS PLAN WAS DESIGNED BY LIC ENGINEER | | ANY REVISIONS SHALL BE SIGNED AND SEALED BY DESIGNER OF | | RECORD. PER FAC 61G15-23.003 | | 5. PROVIDE COMBUSTION AIR CALCULATIONS. PER FBC FG 304 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|