2018-02-15 14:07:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LISTED ON PERMIT APPEARS LOW. PROVIDE COPY OF
 SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 2. RISER DIAGRAM IS CONFUSING. WILL THERE BE A SERVICE
 AT EACH BUILDING ON THIS PROPERTY? HOW MANY METER CANS
 AND DISCONNECTS WILL THERE BE FOR THE PROPERTY? PROVIDE
 COMPLETE RISER DIAGRAM SHOWING THE EXISTING SERVICE AS
 WELL AS THE NEW SERVICE DETAILS FOR ALL SERVICES AT
 THIS ADDRESS, INCLUDING UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. CONDUIT BETWEEN METER AND MAIN BREAKER PANEL SHOULD
 NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE
 CORRECTION. NEC 250.6
 4. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. A NOTE
 WILL SUFFICE. NEC 210.12; FBC RE E3902.16
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 7. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 PROVIDE CORRECTION. NEC 250.56
 8. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3)
 9. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1)
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  