2018-07-27 16:49:17REVIEW FBC-2014 MECHANICAL
 PERMIT #18020063
 7/27/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M204: THE REVISED PLAN DOES NOT SHOW HOW O/A
 IS BEING PROVIDED MECHANICALLY TO THE NEW AVIS OFFICE-
 TABLE 403.3. THE CALCULATION SHOWN IS FOR MECHANICAL
 VENTILATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  