Plan Review Notes
Plan Review Notes For Permit 18020063
Permit Number 18020063
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-06 15:24:181ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18020063
 3/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M204: PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 THE NEW AVIS ROOM- TABLE 403.3
  
 2) SHEET M204: REFER TO SECTION 304.6 AND INDICATE THE
 HEIGHT OF CU-6-2 ABOVE THE FINISHED FLOOR OF THE GARAGE
 FLOOR.
  
 3) M218: PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION
 OF CU-24-2 AND THE RACK- SECTION 301.15.
  
 4) SHOW THE LOCATIONS OF FCU- 22-2, 23-2, AND 24-2.
  
 5) REVISE THE AC AND ENERGY CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  