2018-02-22 16:15:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER |
| PROTECTION IN THE THE ELEVATOR CONTROL ROOMS OF THE |
| AVIS CENTER. |
| |
| THIS IS A FULLY SPRINKLERED BUILDING AND SHALL BE |
| PROVIDED WITH APPLICABLE FIRE SPRINKLER PROTECTION IS |
| ALL LOCATIONS PER NFPA 101 AND 13. |
| |
| PLEASE PROVIDE A REVIEW AND APPLICABLE NOTE. |
| |
| |
| |
| 2) THERE IS NO INDICATION OF FIRE ALARM PROTECTION IN |
| THE AVIS OFFICE. |
| |
| THIS BUILDING IS REQUIRED TO HAVE A COMPLETE FIRE ALARM |
| AND SHALL BE PROVIDED WITH APPLICABLE PROTECTION IS ALL |
| LOCATIONS PER NFPA 101 AND 72. |
| |
| PLEASE PROVIDE A REVIEW AND APPLICABLE NOTE. |
| |
| |
| 3) DOOR 205, AVIS OFFICE, IS SHOWN WITHIN A RATED CMU |
| WALL; HOWEVER, THE DOOR SCHEDULE DOES NOT SHOW ANY |
| RATING. |
| |
| THERE HAS BEEN PREVIOUS DISCUSSION REGARDING THIS LOBBY |
| WALL ABOUT PENETRATIONS BEING RATED AND WHETHER THE |
| WALL WAS RATED OR NOT. |
| |
| PLEASE REVIEW THIS LOBBY WALL AND ENSURE THE DOOR IS |
| APPLICABLY RATED. |
| |
| |
| |
| 4) ANY FIRE SPRINKLER AND/OR FIRE ALARM WORK SHALL BE |
| DONE UNDER SEPARATE SHOP DRAWING REVISIONS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |