2018-02-28 14:34:07DENIED
  
 1. THIS REVIEW IS BASED ON THE 2017 FLORIDA BUILDING
 CODE 6TH EDITION. PLEASE REMOVE ALL REFERENCES TO THE
 2014 FBC 5TH EDITION. WPB AMENDMENTS TO THE FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. CONNECTION UNDER SLAB SHALL BE MADE WITH APPROVED
 FITTING, IF JOINING CAST IRON WITH PVC IT SHALL COMPLY
 WITH SECTIONS P3003.4.1 THROUGH P3003.4.3.
  
 3. THE PLAN SHOWS A BACKFLOW PREVENTION DEVICE AT WATER
 SERVICE BUT NOT REQUIRED. IF ONE WAS TO BE INSTALLED A
 SEPARATE PERMIT APPLICATION, INSPECTION AND
 CERTIFICATION WILL BE REQUIRED AND THE LOCATION SHALL
 BE WITHIN 5' FROM THE CITY METER. IT SHALL BE CERTIFIED
 BY UTILITIES AT OWNERS EXPENSE. WPB AMENDMENTS TO THE
 FBC 105.1.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  