Plan Review Notes For Permit 18020062 |
Permit Number |
18020062 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-28 14:34:07 | DENIED | | | | 1. THIS REVIEW IS BASED ON THE 2017 FLORIDA BUILDING | | CODE 6TH EDITION. PLEASE REMOVE ALL REFERENCES TO THE | | 2014 FBC 5TH EDITION. WPB AMENDMENTS TO THE FBC 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. CONNECTION UNDER SLAB SHALL BE MADE WITH APPROVED | | FITTING, IF JOINING CAST IRON WITH PVC IT SHALL COMPLY | | WITH SECTIONS P3003.4.1 THROUGH P3003.4.3. | | | | 3. THE PLAN SHOWS A BACKFLOW PREVENTION DEVICE AT WATER | | SERVICE BUT NOT REQUIRED. IF ONE WAS TO BE INSTALLED A | | SEPARATE PERMIT APPLICATION, INSPECTION AND | | CERTIFICATION WILL BE REQUIRED AND THE LOCATION SHALL | | BE WITHIN 5' FROM THE CITY METER. IT SHALL BE CERTIFIED | | BY UTILITIES AT OWNERS EXPENSE. WPB AMENDMENTS TO THE | | FBC 105.1. | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | |
|