2018-02-22 09:56:44 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| CURRENT CODES ABOVE) |
| 2. CIRCUIT FOR BATHROOM GFCI RECEPTACLES IS SHOWN AS 15 |
| AMP. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| 3. LIGHTING IN CLOSET IS SHOWN AS A RECESS LIGHT. PER |
| CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. NEC |
| 410.16; FBC RE E4003.12 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |