Plan Review Notes
Plan Review Notes For Permit 18020012
Permit Number 18020012
Review Stop G
Sequence Number 2
Notes
Date Text
2018-03-20 12:06:371) THE SUBMITTED GAS PLAN IS A COPY OF A SIGNED AND
 SEALED PLAN BY AN ENGINEER.PLANS BEARING AND ENGINEER'S
 TITLE BLOCK SHALL ALSO HAVE AN ORIGINAL SIGNATURE AND
 SEAL PER THE FL. ADMIN. CODE 61G15-23.001. SUBMIT TWO
 COPIES OF THE GAS PLAN BEARING THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER.
 2) SHOW THE LOCATION OF THE METAL LOUVERS THAT ARE
 BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS
 CANNOT BE LOCATED IN AN EXTERIOR WALL THAT IS FIRE
 RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED.
 3) THE LOUVERS ARE NOT PERMITTED IN AN EXTERIOR WALL
 WITH A FIRE SEPARATION DISTANCE, TYPE OF CONSTRUCTION,
 AND WHETHER OR NOT THE BUILDING IS SPRINKLERED AS
 LISTED IN TABLE 705.8 OF 2017 FBC-BUILDING.SUBMIT ALL
 REQUIRED INFORMATION. SUBMIT A SITE PLAN SHOWING THE
 DISTANCE OF ALL EXTERIOR WALLS TO ADJACENT PROPERTY
 LINES. WPB AMEND. TO FBC SEC.107.2.1.
 4) SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS.
 5) THIS PLAN SHALL BE TAKEN TO THE ENGINEER OF RECORD
 TO BE SIGNED AND SEALED AND SUBMITTED AS CORRECTIONS
 ALONG WITH ALL OTHER CORRECTIONS UNDER THE MASTER
 PERMIT NUMBER 18020521. THIS GAS PERMIT CANNOT BE
 ISSUED UNTIL THE MASTER PERMIT HAS BEEN APPROVED.
 6) COPIES OF EQUIPMENT SPECIFICATIONS HAVE BEEN
 SUBMITTED FOR TWO DIFFERENT PIECES OF EQUIPMENT BY TWO
 DIFFERENT MANUFACTURERS. THE PLANS SHOW A ROTATING RACK
 OVEN BUT SPECS HAVE ALSO BEEN PROVIDED FOR A DOUBLE
 RACK OVEN. WHICH ONE IS BEING INSTALLED? CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
 .