2018-03-20 12:06:37 | 1) THE SUBMITTED GAS PLAN IS A COPY OF A SIGNED AND |
| SEALED PLAN BY AN ENGINEER.PLANS BEARING AND ENGINEER'S |
| TITLE BLOCK SHALL ALSO HAVE AN ORIGINAL SIGNATURE AND |
| SEAL PER THE FL. ADMIN. CODE 61G15-23.001. SUBMIT TWO |
| COPIES OF THE GAS PLAN BEARING THE ORIGINAL SEAL AND |
| SIGNATURE OF THE ENGINEER. |
| 2) SHOW THE LOCATION OF THE METAL LOUVERS THAT ARE |
| BEING INSTALLED FOR THE COMBUSTION AIR. THE LOUVERS |
| CANNOT BE LOCATED IN AN EXTERIOR WALL THAT IS FIRE |
| RATED AS THE FIRE RATING OF THE WALL MUST BE |
| MAINTAINED. |
| 3) THE LOUVERS ARE NOT PERMITTED IN AN EXTERIOR WALL |
| WITH A FIRE SEPARATION DISTANCE, TYPE OF CONSTRUCTION, |
| AND WHETHER OR NOT THE BUILDING IS SPRINKLERED AS |
| LISTED IN TABLE 705.8 OF 2017 FBC-BUILDING.SUBMIT ALL |
| REQUIRED INFORMATION. SUBMIT A SITE PLAN SHOWING THE |
| DISTANCE OF ALL EXTERIOR WALLS TO ADJACENT PROPERTY |
| LINES. WPB AMEND. TO FBC SEC.107.2.1. |
| 4) SHOW THE SIZE OF THE LOUVER(S) ON THE PLANS. |
| 5) THIS PLAN SHALL BE TAKEN TO THE ENGINEER OF RECORD |
| TO BE SIGNED AND SEALED AND SUBMITTED AS CORRECTIONS |
| ALONG WITH ALL OTHER CORRECTIONS UNDER THE MASTER |
| PERMIT NUMBER 18020521. THIS GAS PERMIT CANNOT BE |
| ISSUED UNTIL THE MASTER PERMIT HAS BEEN APPROVED. |
| 6) COPIES OF EQUIPMENT SPECIFICATIONS HAVE BEEN |
| SUBMITTED FOR TWO DIFFERENT PIECES OF EQUIPMENT BY TWO |
| DIFFERENT MANUFACTURERS. THE PLANS SHOW A ROTATING RACK |
| OVEN BUT SPECS HAVE ALSO BEEN PROVIDED FOR A DOUBLE |
| RACK OVEN. WHICH ONE IS BEING INSTALLED? CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| . |