2018-02-07 06:28:58 | DENIED |
| |
| 1. ON GAS NOTES, THE SPECIFICATION FOR PLUMBING CODE |
| COMPLIANCE SAY 2014 FBC FUEL GAS ON PAGE P-3 BUT SHOULD |
| IT REFER TO 2017 FBC FUEL GAS. RISER SHOWS 1 1/2" FROM |
| THE METER, GAS NOTES SHOW 1-/2", THIS IS A TYPO THAT |
| REQUIRES CORRECTION. PLEASE MAKE A NOTE TO REFLECT |
| THESE CORRECTIONS. FBC WPB AMENDMENTS 107.2.1. |
| 2. SHOW WHAT TYPE OF PROTECTIVE COATING AGAINST |
| CORROSION ON PIPE AND FITTINGS. 2017 FBC FUEL GAS SEC |
| 403.8, 404.11. |
| 3. SHOW DRIPS LEG AND LOCATIONS ON RISER DIAGRAM, |
| SEDIMENT TRAP AND SLOPED PIPING 2017 FBC FUEL GAS SEC. |
| 408.1, 404.2, 404.3 AND 404.4. |
| 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. |
| 5. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC. 402.2 AND |
| 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. 2017 FUEL |
| GAS SEC.305.1. |
| 6. EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE |
| BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE |
| UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS. |
| 10.4, 10.5 OF NFPA 96-08. |
| 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC FUEL |
| GAS SEC. 304.9.3 |
| 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM ON THE NEW CODE 2017 FBC |
| FUE GAS TABLE 402.4. (1). TABLES SUBMITTED ARE 402.4(1) |
| BUT GAS NOTES REFER TO 402.4(2) PLEASE CLARIFY. |
| 9. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH |
| THE EXTERIOR WILL BE PROTECTED. 2017 FBC FUEL GAS SEC. |
| 404.7. |
| |