Plan Review Notes
Plan Review Notes For Permit 18020012
Permit Number 18020012
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-07 06:28:58DENIED
  
 1. ON GAS NOTES, THE SPECIFICATION FOR PLUMBING CODE
 COMPLIANCE SAY 2014 FBC FUEL GAS ON PAGE P-3 BUT SHOULD
 IT REFER TO 2017 FBC FUEL GAS. RISER SHOWS 1 1/2" FROM
 THE METER, GAS NOTES SHOW 1-/2", THIS IS A TYPO THAT
 REQUIRES CORRECTION. PLEASE MAKE A NOTE TO REFLECT
 THESE CORRECTIONS. FBC WPB AMENDMENTS 107.2.1.
 2. SHOW WHAT TYPE OF PROTECTIVE COATING AGAINST
 CORROSION ON PIPE AND FITTINGS. 2017 FBC FUEL GAS SEC
 403.8, 404.11.
 3. SHOW DRIPS LEG AND LOCATIONS ON RISER DIAGRAM,
 SEDIMENT TRAP AND SLOPED PIPING 2017 FBC FUEL GAS SEC.
 408.1, 404.2, 404.3 AND 404.4.
 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
 5. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC. 402.2 AND
 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. 2017 FUEL
 GAS SEC.305.1.
 6. EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC FUEL
 GAS SEC. 304.9.3
 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM ON THE NEW CODE 2017 FBC
 FUE GAS TABLE 402.4. (1). TABLES SUBMITTED ARE 402.4(1)
 BUT GAS NOTES REFER TO 402.4(2) PLEASE CLARIFY.
 9. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH
 THE EXTERIOR WILL BE PROTECTED. 2017 FBC FUEL GAS SEC.
 404.7.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved