Plan Review Notes
Plan Review Notes For Permit 18020006
Permit Number 18020006
Review Stop B
Sequence Number 4
Notes
Date Text
2018-07-03 17:40:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC B 1609
  
 1. THE ENGINEER'S LETTER STATES THAT THE "COMPOSITE
 PANELS" HAVE NO PRODUCT APPROVAL.
  
 THE LETTER SHOULD BE SPECIFIC AS TO PRODUCT, AND THAT
 THE PRODUCT DOES HAVE AN NOA BUT FOR USE AS A WALL
 PANEL, NOT A ROOF PANEL. REVISE TO REFERENCE.
  
 2. THE LETTER STATES THAT THE PANELS ARE ADJUDGED
 "STRUCTURALLY EQUAL" TO METL-SPAN CFR PANELS. THE TWO
 PRODUCTS ARE DIFFERENT (FOAM DENSITY, STEEL GAGE);
 INCLUDE THE DIFFERENCES IN THE LETTER.
  
 3. THE LETTER STATES THAT THE PRODUCT WILL "SPAN 48"".
 IT IS NOT CLEAR WHERE THIS IS; THE ROOF PANEL NOA SPANS
 60", WALL SPAN DOES NOT APPEAR RELEVANT; CLARIFY OR
 REMOVE.
  
 4. THE LETTER SHOULD SPECIFICALLY STATE THAT THE WALL
 PANEL NOA IS ACCEPTABLE FOR USE AS A ROOF PANEL.
  
 5. THE PLANS APPEAR TO SHOW THE ROOF PANELS SECURED TO
 THE WALL PANELS WITH "TRIM" AND NO OTHER SUPPORT AT
 EACH END. SEE THE ROOF PANEL NOA, PAGE 3, HIGH EAVE
 DETAIL AND EVE DETAIL. THE INSTALLATION SHOULD BE
 CONSISTENT WITH THE NOA OR A DETAIL WITH SIMILAR
 SUPPORT PROVIDED.
  
 6. IT IS MY UNDERSTANDING THAT A ROOF COVERING WAS
 INSTALLED; PROVIDE ADDITIONAL INFORMATION - PRODUCT
 APPROVAL, METHOD OF INSTALLATION. REVISE PLAN TO
 INCLUDE THE ROOF COVERING.
  
 7. PROVIDE DESIGN PRESSURES FOR THE ROOF. SEE SHEET 1
 OF 3, ROOF PANEL NOA. REVISE PLAN TO PROPOSE PERLIN
 SUPPORT AS NEEDED FOR SPECIFIED DESIGN PRESSURES.
  
 8. SHEET 1, THE EXPANSION BOLT IS SHOWN GRAPHICALLY TOO
 CLOSE TO THE EDGE OF THE CONCRETE. REVISE TO SHOW
 DISTANCE OF EACH BOLT TO EDGE, AND DISTANCE BETWEEN
 BOLTS. PROVIDE THE PRODUCT APPROVAL FOR THE BOLTS SO
 REQUIRED SEPARATION AND EDGE DISTANCE CAN BE CONFIRMED.
 THE WAY THE DETAIL IS DRAWN, FAILURE OF THE CONCRETE AT
 THE TOP IS POSSIBLE.
  
 9. THE NOA FOR THE ROOF PANELS, HIGH EAVE DETAIL AND
 EAVE DETAIL, SHOW FASTENERS FROM "EAVE STRUCTURE BY
 OTHERS" TO THE WALL PANEL, BUT DOES NOT SPECIFY
 SPACING. REVISE PLAN TO INCLUDE.
  
 10. A MECHANICAL UNIT IS SHOWN ABOVE THE COOLER. HOW
 WILL THIS BE ACCESSED FOR SERVICE? FBC B TABLE 1607.1,
 IT APPEARS THAT THE ONLY ACCESS IS OVER THE TOP OF THE
 COOLER, BUT THE COOLER ROOF DOES NOT APPEAR TO BE
 DESIGNED FOR THE REQUIRED LOAD OF 300# PSF.
  
 11. FBC B TABLE 1607.1, REVISE PLAN TO CLARIFY THAT THE
 ROOF MEETS THE LIVE LOAD REQUIREMENT OF 20# PSF.
  
 12. AFTER PERMIT IS ISSUED AND INSTALLATION IS
 COMPLETE, AN ENGINEER'S INSPECTION AND LETTER/REPORT
 WILL BE REQUIRED DUE TO THE UNUSUAL NATURE OF THE
 CONSTRUCTION, FBC 110.3.9.
  
 13. FOR THE WALL PANELS, ON THE PRODUCT APPROVAL
 INDICATE
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved