2018-05-10 16:30:42 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18020006 |
| 5/10/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE USE OF THE KINGSPAN 300 INSULATED WALL PANELS TO |
| FORM THE ROOF OF THE WALK-IN COOLER IS STILL IN |
| QUESTION BY THE BUILDING DEPARTMENT. AS PREVIOUSLY |
| STATED IN THE1ST AND 2ND REVIEWS, THE ENGINEERING |
| REPORT CONTAINED IN THE MIAMI-DADE NOA #16-0706.08 |
| INDICATES THE PANELS HAVE BEEN EVALUATED AS NON BEARING |
| EXTERIOR WALL PANELS. THEY HAVE NOT BEEN EVALUATED AS A |
| ROOF |
| |
| PANEL. IN RESPONSE, THE PROJECT MANAGER HAS SUBMITTED A |
| DOCUMENT FROM THE MANUFACTURER TITLED "UNIFORM WIND + |
| THERMAL LOAD". THIS STRUCTURAL ANALYSIS APPEARS TO BE |
| FOR AN INDIVIDUAL WALL PANEL, AND DOES NOT ADDRESS THE |
| USE OF THE PANEL AS A ROOF PANEL. FURTHER, THE ANALYSIS |
| IS NOT SITE SPECIFIC AND IS NOT SIGNED AND SEALED BY A |
| FLORIDA REGISTERED ENGINEER AS REQUIRED BY FLORIDA |
| |
| STAUTE 471, AND FAC 16G15-23.002. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |