2018-05-10 16:30:423RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18020006
 5/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE USE OF THE KINGSPAN 300 INSULATED WALL PANELS TO
 FORM THE ROOF OF THE WALK-IN COOLER IS STILL IN
 QUESTION BY THE BUILDING DEPARTMENT. AS PREVIOUSLY
 STATED IN THE1ST AND 2ND REVIEWS, THE ENGINEERING
 REPORT CONTAINED IN THE MIAMI-DADE NOA #16-0706.08
 INDICATES THE PANELS HAVE BEEN EVALUATED AS NON BEARING
 EXTERIOR WALL PANELS. THEY HAVE NOT BEEN EVALUATED AS A
 ROOF
  
 PANEL. IN RESPONSE, THE PROJECT MANAGER HAS SUBMITTED A
 DOCUMENT FROM THE MANUFACTURER TITLED "UNIFORM WIND +
 THERMAL LOAD". THIS STRUCTURAL ANALYSIS APPEARS TO BE
 FOR AN INDIVIDUAL WALL PANEL, AND DOES NOT ADDRESS THE
 USE OF THE PANEL AS A ROOF PANEL. FURTHER, THE ANALYSIS
 IS NOT SITE SPECIFIC AND IS NOT SIGNED AND SEALED BY A
 FLORIDA REGISTERED ENGINEER AS REQUIRED BY FLORIDA
  
 STAUTE 471, AND FAC 16G15-23.002.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  