2018-05-05 09:52:59 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 3RD REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. JOB ADDRESS LISTED ON PLAN REVIEW REQUEST FORM IS |
| 538 NORTHWOOD RD. CORRECT ADDRESS FOR THIS PROJECTL IS |
| 3815 S DIXIE HWY. PLEASE CLARIFY. |
| 2. CONTRACTOR LISTED ON LATEST PLAN REVIEW REQUEST FORM |
| IS EDRIK BANDEZ, GENERAL CONTRACTOR, CGC1522589. |
| CONTRACTOR FOR MECHANICAL SUB-PERMIT IS EVID VALERO, |
| CAC1817915. PLEASE CLARIFY. |
| 3. RESPONSE FROM METRO DESIGN GROUP IN RESPONSE TO PLAN |
| REVIEW COMMENT DENYING THE USE OF KINGSPAN INSULATED |
| PANELS TO BE USED FOR THE ROOF OF THE WALK-IN COOLER |
| STATES "THE ROOF HAS BEEN INSTALLED AND INSPECTED UNDER |
| THE BUILDING MASTER ROOFING PERMIT". NO RECORD CAN BE |
| FOUND OF A PRODUCT APPROVAL FOR THESE COMPOSITE WALL |
| PANELS BEING SUBMITTED AND/OR APPROVED FOR ANY PREVIOUS |
| PERMIT. ALSO, THERE IS NO INSPECTION HISTORY THAT THESE |
| INSULATED PANELS WRE INSPECTED AND APPROVED FOR THE |
| APPLIED USE. |
| PROVIDE SITE SPECIFIC ENGINEERING FOR THE KINGSPAN |
| INSULATED PANELS TO BE USED AS A ROOF SYSTEM COMPONENT. |
| DEMONSTRATE THAT THE PANELS, WHEN USED IN THIS |
| APPLICATION, WILL MEET OR EXCEED THE ANTICIPATED WIND |
| LOADS FOR THEIR LOCATION AND USE. |
| |
| PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| 61G15-23.001. |
| |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| F.S. 553.80 (2) (B) |
| (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| |
| |
| |
| |