Plan Review Notes
Plan Review Notes For Permit 18020006
Permit Number 18020006
Review Stop B
Sequence Number 3
Notes
Date Text
2018-05-05 09:52:59BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. JOB ADDRESS LISTED ON PLAN REVIEW REQUEST FORM IS
 538 NORTHWOOD RD. CORRECT ADDRESS FOR THIS PROJECTL IS
 3815 S DIXIE HWY. PLEASE CLARIFY.
 2. CONTRACTOR LISTED ON LATEST PLAN REVIEW REQUEST FORM
 IS EDRIK BANDEZ, GENERAL CONTRACTOR, CGC1522589.
 CONTRACTOR FOR MECHANICAL SUB-PERMIT IS EVID VALERO,
 CAC1817915. PLEASE CLARIFY.
 3. RESPONSE FROM METRO DESIGN GROUP IN RESPONSE TO PLAN
 REVIEW COMMENT DENYING THE USE OF KINGSPAN INSULATED
 PANELS TO BE USED FOR THE ROOF OF THE WALK-IN COOLER
 STATES "THE ROOF HAS BEEN INSTALLED AND INSPECTED UNDER
 THE BUILDING MASTER ROOFING PERMIT". NO RECORD CAN BE
 FOUND OF A PRODUCT APPROVAL FOR THESE COMPOSITE WALL
 PANELS BEING SUBMITTED AND/OR APPROVED FOR ANY PREVIOUS
 PERMIT. ALSO, THERE IS NO INSPECTION HISTORY THAT THESE
 INSULATED PANELS WRE INSPECTED AND APPROVED FOR THE
 APPLIED USE.
 PROVIDE SITE SPECIFIC ENGINEERING FOR THE KINGSPAN
 INSULATED PANELS TO BE USED AS A ROOF SYSTEM COMPONENT.
 DEMONSTRATE THAT THE PANELS, WHEN USED IN THIS
 APPLICATION, WILL MEET OR EXCEED THE ANTICIPATED WIND
 LOADS FOR THEIR LOCATION AND USE.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
  
  
  