2018-03-14 18:02:37 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #18020006 |
| 3/14/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. I HAVE |
| REPRINTED IT BELOW WITH SOME ADDITIONAL INFORMATION: |
| |
| NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION FOR |
| THE THERMALSPAN 300 INSULATED METAL WALL PANELS. THERE |
| ARE NO DETAILS OR CERTIFICATIONS ON THE NOA FOR THE |
| ROOF PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR |
| ATTACHMENT AND SUPPORT OF ROOF PANELS. |
| |
| PLEASE REFER TO THE ENGINEERING REPORT & DRAWINGS FOR |
| THE THERMALSPAN 300 INSULATED METAL WALL PANELS |
| ATTACHED WITH THE NOA. ON PAGE 2 OF THE DOCUMENT SEE |
| ITEM 3.0 EVALUATED USES, AND 4.0 ASSEMBLY DESCRIPTION. |
| THE ENGINEER IS CLEARLY STATING THAT THESE PANELS ARE |
| NON-LOAD BEARING AND CAN ONLY BE INSTALLED VERTICALLY. |
| THE DRAWING ON PLAN SHEET 2 IS DEPICTING AN |
| |
| INSTALLATION INCONSISTENT WITH THE ENGINEERING |
| CERTIFICATION, AND BEYOND THE LIMITATIONS OF USE FOR |
| THE PANEL. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |