2018-03-14 18:02:371ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18020006
 3/14/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #3 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW WITH SOME ADDITIONAL INFORMATION:
  
 NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION FOR
 THE THERMALSPAN 300 INSULATED METAL WALL PANELS. THERE
 ARE NO DETAILS OR CERTIFICATIONS ON THE NOA FOR THE
 ROOF PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR
 ATTACHMENT AND SUPPORT OF ROOF PANELS.
  
 PLEASE REFER TO THE ENGINEERING REPORT & DRAWINGS FOR
 THE THERMALSPAN 300 INSULATED METAL WALL PANELS
 ATTACHED WITH THE NOA. ON PAGE 2 OF THE DOCUMENT SEE
 ITEM 3.0 EVALUATED USES, AND 4.0 ASSEMBLY DESCRIPTION.
 THE ENGINEER IS CLEARLY STATING THAT THESE PANELS ARE
 NON-LOAD BEARING AND CAN ONLY BE INSTALLED VERTICALLY.
 THE DRAWING ON PLAN SHEET 2 IS DEPICTING AN
  
 INSTALLATION INCONSISTENT WITH THE ENGINEERING
 CERTIFICATION, AND BEYOND THE LIMITATIONS OF USE FOR
 THE PANEL.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  