2018-02-09 11:25:46 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #18020006 |
| 2/9/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1, DESIGN CRITERIA: THE FLORIDA BUILDING CODE |
| SIXTH EDITION-2017 WENT INTO EFFECT ON JAN.1, 2017. |
| THIS PERMIT APPLICATION AND PLANS WERE SUBMITTED AFTER |
| THAT DATE. PLEASE UPDATE THE DESIGN PARAMETERS FOR THE |
| PROJECT, AND THE DESIGN CRITERIA LISTED ON SHEET A1 TO |
| BE IN COMPLIANCE WITH THE CURRENT CODES. |
| |
| 2) SHEET 1: THE NOA #13-0909.11 HAS BEEN SUPERSEDED BY |
| #16-0706.08. PLEASE SUBMIT COPIES OF THE NOA WITH |
| APPROVAL STAMPS BY THE EOR. |
| |
| 3) NOA #16-0706.08 PROVIDES ENGINEERING CERTIFICATION |
| FOR NONBEARING EXTERIOR WALL PANELS. THERE ARE NO |
| DETAILS OR CERTIFICATIONS ON THE NOA FOR THE ROOF |
| PANELS, AND NO TYPICAL DETAILS ARE PROVIDED FOR |
| ATTACHMENT ABND SUPPORT OF ROOF PANELS. PLEASE NOTE |
| THAT THE NOA IS FOR THERMALSPAN 300 PANEL, BUT THE PLAN |
| INDICATES ECO-FICIENT PANELS. |
| |
| 4) PROVIDE AN ATTACHMENT DETAIL ON THE PLAN FOR THE |
| VINYL RAIN COVER, AND SUPPORT A PRODUCT DATA SHEET |
| APPROVED BY THE EOR. |
| |
| 5) PROVIDE ENGINEERED DETAILS FOR THE WALL BRACKET. |
| CLARIFY IF THE BRACKET IS TO BE SITE BUILT, OR IS THE |
| BRACKET A MANUFACTURED PRODUCT THAT HAS A FL. PRODUCT |
| APPROVAL OR A MIAMI-DADE NOA? |
| |
| 6) SPECS FOR THE FJAF-0108-TAC-052 CONDENSER AND THE |
| LSCO78TFC EVAPORATOR NOT SUBMITTED. |
| |
| PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR PENDING |
| RESUBMITTAL OF CORRECTED PLANS AND DOCUMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |