Plan Review Notes For Permit 18011268 |
Permit Number |
18011268 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-01 15:18:46 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: FBC 6TH EDITION (2017). | | | | 1- ROOF TILE NOA 12-0904.08 SUBMITTED WITH FLORIDA | | PRODUCT APPROVAL FL601-R13 EXPIRED ON 01/02/18. NEED TO | | PROVIDE CURRENT PRODUCT APPROVAL (2 COPIES) AS REQUIRED | | BY FAC 61G20-3.001. | | NOTE: I CONTACTED THE FLORIDA PRODUCT APPROVAL STAFF TO | | INFORM THEM ABOUT THIS ISSUE SO THEY CAN UPDATE THE | | INFORMATION. | | | | 2- TU PUS FLORIDA PRODUCT APPROVAL FL5259-R27: CLEARLY | | MARK WHICH UNDERLAYMENT SYSTEM ON PAGE 7 OF 14 IS GOING | | TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|