2018-02-20 14:38:15 | DENIED |
| |
| 1. TANK-LESS WATER HEATER REQUIRES A SEPARATE PERMIT |
| FOR GAS. INDICATE ON THE PLAN IF THE TANK-LESS WATER |
| HEATER IS REPLACING AN EXISTING TANK-LESS WATER HEATER |
| OR IS IT REPLACING A STORAGE TANK TYPE WATER HEATER OR |
| IS IT BEING ADDED TO THE EXISTING HOT WATER SYSTEM? WPB |
| AMENDMENTS TO THE FBC SEC 105.1 |
| 2. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING A PIPING |
| RISER DIAGRAM AND A DRAWING SHOWING THE LOCATION OF TWH |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. INDICATE ON THE PLAN IF |
| THE TANK-LESS WATER HEATER IS THE ONLY GAS APPLIANCE IN |
| THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS RISER |
| SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH |
| APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS AND |
| THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS |
| ALSO APPLY TO A NEW GAS SYSTEM. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMENDMENTS TO THE FBC SEC 107.2.1. |
| 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC R |
| SEC G2413.3. |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC R SEC G2413.2. |
| 5. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC 107.2.1. |
| 6. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC R SEC |
| G2412.4, G2412.8, G2413.1, G2413.2, & G2413.3. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| [email protected] |
| 561-805-6720 |
| |
2018-02-05 10:51:23 | NO GAS PLAN HAVE BEEN SUBMITTED |