Plan Review Notes For Permit 18011231 |
Permit Number |
18011231 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-02 09:05:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THE SUBMITTED PLANS INDICATE FLEXHEAD DROPS. THERE | | IS NO INDICATION THAT THESE NEW HEADS ARE REPLACING | | EXISTING FLEXHEAD DROPS. THERE IS ALSO NO INDICATION | | HOW THESE NEW FLEXHEAD DROPS AFFECT THE EXISTING | | FRICTION LOSS CALCULATIONS. | | | | PLEASE REVIEW AND ENSURE THAT THESE NEW FLEXHEAD DROPS | | DO NOT NEGATIVELY IMPACT THE PERFORMACE OF THE SYSTEM | | BEYOND ITS DESIGN CAPABILITIES. | | | | | | | | 2) THE SUBMITTED EQUIPMENT SPEC DO NOT CONTAIN ANY SPEC | | SHEETS/INFORMATION ON THE PROPOSED FLEXHEAD DROPS. | | | | PLEASE PROVIDE TO REVIEW AND CONFIRM # 1 ABOVE. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | |
|