2018-02-02 09:05:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE SUBMITTED PLANS INDICATE FLEXHEAD DROPS. THERE
 IS NO INDICATION THAT THESE NEW HEADS ARE REPLACING
 EXISTING FLEXHEAD DROPS. THERE IS ALSO NO INDICATION
 HOW THESE NEW FLEXHEAD DROPS AFFECT THE EXISTING
 FRICTION LOSS CALCULATIONS.
  
 PLEASE REVIEW AND ENSURE THAT THESE NEW FLEXHEAD DROPS
 DO NOT NEGATIVELY IMPACT THE PERFORMACE OF THE SYSTEM
 BEYOND ITS DESIGN CAPABILITIES.
  
  
  
 2) THE SUBMITTED EQUIPMENT SPEC DO NOT CONTAIN ANY SPEC
 SHEETS/INFORMATION ON THE PROPOSED FLEXHEAD DROPS.
  
 PLEASE PROVIDE TO REVIEW AND CONFIRM # 1 ABOVE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  