2018-04-06 10:36:06RESIDENTIAL (R3) REVISION FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 RECEIVED E-MAIL FROM JOE DARSCH FROM ASTRO AIR INC. THE
 SAME INFORMATION WAS SUBMITTED ON THE THIRD REVIEW WAS
 E-MAILED THIS TIME. NEED TO ADDRESS THE COMMENTS FROM
 THIRD REVIEW. SEE COPY OF COMMENTS BELOW AND RESUBMIT.
  
  
 RESIDENTIAL (R3) REVISION THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- BASED ON THE EQUIPMENT SIZING CALCULATIONS SUBMITTED
 IT LOOKS LIKE THE A/C EQUIPMENT MAY BE OVER-SIZED. THE
 TOTAL COOLING CALCULATIONS CALL FOR 31453 BTUH.
 THEREFORE, A 3 TON UNIT MAY BE THE CORRECT SIZE OF UNIT
 REQUIRED. THE SPECIFIED EQUIPMENT IS A 4 TON UNIT. THE
 EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER THAN
 THE TOTAL LOAD CALCULATED. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). EQUIPMENT NEEDS TO BE
 REVISED ACCORDINGLY.
  
 RESPONSE:
 CLARIFY WHY SUBMITTING DIFFERENT EQUIPMENT SIZING
 CALCULATIONS. PREVIOUS CALCULATIONS LOOKED TO BE OK.
 THE ONLY THING WAS THAT SELECTED EQUIPMENT WAS
 OVERSIZED. CALCULATIONS SUBMITTED NOW HAVE A TOTAL
 COOLING LOAD OF 25459 BTUH. THEREFORE, THE 36000 BTUH
 IS OVERSIZED BASED ON THIS CALCULATIONS. REVISE AS
 REQUIRED. PROVIDE COORDINATED INFORMATION.
  
 2- PERSON RESPONSIBLE FOR THE A/C PLAN TO PROVIDE NAME
 AND SIGNATURE ON THE PLAN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  