Plan Review Notes For Permit 18011193 |
Permit Number |
18011193 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-02-22 17:08:14 | RESIDENTIAL (R3) REVISION SECOND MECHANICAL REVIEW | | CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | 1- BASED ON THE EQUIPMENT SIZING CALCULATIONS SUBMITTED | | IT LOOKS LIKE THE A/C EQUIPMENT MAY BE OVER-SIZED. THE | | TOTAL COOLING CALCULATIONS CALL FOR 31453 BTUH. | | THEREFORE, A 3 TON UNIT MAY BE THE CORRECT SIZE OF UNIT | | REQUIRED. THE SPECIFIED EQUIPMENT IS A 4 TON UNIT. THE | | EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER THAN | | THE TOTAL LOAD CALCULATED. SEC. R403.6.1.1 FBC-ENERGY | | CONSERVATION, 5TH EDITION (2014). EQUIPMENT NEEDS TO BE | | REVISED ACCORDINGLY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|