2018-02-22 17:08:14RESIDENTIAL (R3) REVISION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- BASED ON THE EQUIPMENT SIZING CALCULATIONS SUBMITTED
 IT LOOKS LIKE THE A/C EQUIPMENT MAY BE OVER-SIZED. THE
 TOTAL COOLING CALCULATIONS CALL FOR 31453 BTUH.
 THEREFORE, A 3 TON UNIT MAY BE THE CORRECT SIZE OF UNIT
 REQUIRED. THE SPECIFIED EQUIPMENT IS A 4 TON UNIT. THE
 EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER THAN
 THE TOTAL LOAD CALCULATED. SEC. R403.6.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). EQUIPMENT NEEDS TO BE
 REVISED ACCORDINGLY.
  