2018-02-06 17:19:52RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- DRAWING SUBMITTED NEED TO HAVE THE SEAL AND
 SIGNATURE OF THE ARCHITECT OF RECORD SHOWN ON THE TITLE
 BLOCK AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED
 BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). ONLY SUMMARY SHEETS WERE SUBMITTED. PROVIDE
 COMPLETE WORKSHEETS BASED ON THE ORIENTATION OF THE
 BUILDING.
  
 3- AHRI NUMBER SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS DOESN'T MATCH AHRI NUMBER SHOWN ON THE
 AHRI CERTIFICATED SUBMITTED AND SHOWN ON PLAN
 SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC. 107.3.5.3
 CITY AMENDMENTS.
  
  