2018-02-06 17:19:52 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- DRAWING SUBMITTED NEED TO HAVE THE SEAL AND | | SIGNATURE OF THE ARCHITECT OF RECORD SHOWN ON THE TITLE | | BLOCK AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. | | | | 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED | | ON THE ACTUAL ORIENTATION OF THE BUILDING AS REQUIRED | | BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION | | (2014). ONLY SUMMARY SHEETS WERE SUBMITTED. PROVIDE | | COMPLETE WORKSHEETS BASED ON THE ORIENTATION OF THE | | BUILDING. | | | | 3- AHRI NUMBER SHOWN ON THE EQUIPMENT SIZING | | CALCULATIONS DOESN'T MATCH AHRI NUMBER SHOWN ON THE | | AHRI CERTIFICATED SUBMITTED AND SHOWN ON PLAN | | SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC. 107.3.5.3 | | CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|