Plan Review Notes
Plan Review Notes For Permit 18011120
Permit Number 18011120
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-02 06:35:021) SUBMIT MANUFACTURING SPECIFICATIONS FOR THE
 GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE UNDERGROUND TANK IS SHOWN IN THE MIDDLE OF
 DRIVEWAY ON THE SURVEY. INDICATE HOW THE LP TANK IS
 GOING TO BE PROTECTED FROM DAMAGE. PROTECTION SHALL BE
 PROVIDED IN ACCCORDANCE WITH 2014 NFPA 58 SEC.6.6.6.1
 (E).
 NFPA 58 - 6.6.6.1* ASME CONTAINER ASSEMBLIES INTENDED
 FOR UNDERGROUND INSTALLATION, INCLUDING INTERCHANGEABLE
 ABOVEGROUND ? UNDERGROUND CONTAINER ASSEMBLIES, SHALL
 BE INSTALLED UNDERGROUND IN ACCORDANCE WITH 6.6.6.1(A)
 THROUGH 6.6.6.1(M).
 (E) THE INSTALLATION OF A BURIED CONTAINER SHALL
 INCLUDE PROTECTION
 FOR THE CONTAINER AND PIPING AGAINST PHYSICAL DAMAGE
 FROM VEHICULAR TRAFFIC.
 3) INDICATE HOW THE FIRST STAGE REGULATOR IS GOING TO
 BE VENTED WHEN THE TANK IS IN THE MIDDLE OF THE
 DRIVEWAY.THE VENT SHALL COMPLY WITH NFPA 58 SEC.
 6.6.6.1 ( H) - THE DISCHARGE OF THE REGULATOR VENT
 SHALL BE ABOVE THE
 HIGHEST PROBABLE WATER LEVEL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  