2018-02-12 11:04:232ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL
 PERMIT #18011090
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESCHECK ENERGY COMPLIANCE SUBMITTAL IS
 INCOMPLETE, AND IS ALSO UNDER THE OUTDATED 2014 CODE.
 PLEASE NOTE THAT THE FLORIDA ENERGY CODE SIXTH EDITION-
 2017 WENT INTO EFFECT JAN.1, 2018. THE ENERGY SUBMITTAL
 IS ALSO MISSING COMPLIANCE DATA FOR THE AC SYSTEM AND
 SHOWS "NAPLES, FLORIDA" AS THE PROJECT LOCATION. PLEASE
 REMOVE THE 2014 ENERGYGAUGE DISPLAY CARD FROM
  
 THE RESCHECK SUBMITTAL. THE DISPLAY CARD IS USED ONLY
 WHEN SUBMITTED AN ENERGYGAUGE COMPLIANCE REPORT.
  
 2) THE 10X6 TRANSFER GRILLS ARE UNDERSIZED FOR 150
 CFMS. THE GRILLS SHALL BE MINIMUM 75 SQ. INCHES-
 SECTION M1602 FBC-17 RESIDENTIAL.
  