Plan Review Notes For Permit 18011090 |
Permit Number |
18011090 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-02-12 11:04:23 | 2ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL | | PERMIT #18011090 | | 2/12/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE RESCHECK ENERGY COMPLIANCE SUBMITTAL IS | | INCOMPLETE, AND IS ALSO UNDER THE OUTDATED 2014 CODE. | | PLEASE NOTE THAT THE FLORIDA ENERGY CODE SIXTH EDITION- | | 2017 WENT INTO EFFECT JAN.1, 2018. THE ENERGY SUBMITTAL | | IS ALSO MISSING COMPLIANCE DATA FOR THE AC SYSTEM AND | | SHOWS "NAPLES, FLORIDA" AS THE PROJECT LOCATION. PLEASE | | REMOVE THE 2014 ENERGYGAUGE DISPLAY CARD FROM | | | | THE RESCHECK SUBMITTAL. THE DISPLAY CARD IS USED ONLY | | WHEN SUBMITTED AN ENERGYGAUGE COMPLIANCE REPORT. | | | | 2) THE 10X6 TRANSFER GRILLS ARE UNDERSIZED FOR 150 | | CFMS. THE GRILLS SHALL BE MINIMUM 75 SQ. INCHES- | | SECTION M1602 FBC-17 RESIDENTIAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|