2018-02-01 08:11:53 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- WIND LOAD CALCULATIONS SUBMITTED: |
| A) NEED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| B) REVISE THE MINIMUM EDGE DISTANCE. ACCORDING TO |
| FOOTNOTE OF FIGURE R301.2(7) FBC-RESIDENTIAL, 6TH |
| EDITION (2017) THE MINIMUM EDGE DISTANCE "A" IS 4'-0" |
| IN ALL CASES NOT 3'-0". REVISE AS REQUIRED. |
| |
| 2- REVISE INSTALLATION SCHEDULE SUBMITTED. |
| A) OPENINGS #4 AND #5 SPECIFY ANCHOR TYPE "A" WITH A |
| SPACING OF 14" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR |
| SCHEDULE TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS |
| SUBMITTED THIS ANCHOR REQUIRES 3.000PSI CONCRETE |
| STRENGTH. IT LOOKS LIKE THE BUILD OUT TRACK IS GOING TO |
| BE MOUNTED ON THE EDGE OF THE CONCRETE SLAB. TYPICALLY |
| THE CONCRETE SLABS FOR RESIDENTIAL PROJECTS ARE |
| DESIGNED FOR 2500PSI CONCRETE STRENGTH. REVISE THE |
| ANCHOR TYPE AND SPACING OR PROVIDE PROOF THAT THE |
| CONCRETE STRENGTH IS 3.000PSI. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) OPENINGS #8 SPECIFY ANCHOR TYPE "A" WITH A SPACING |
| OF 9" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR SCHEDULE |
| TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS SUBMITTED |
| THIS ANCHOR REQUIRES 3.000PSI CONCRETE STRENGTH. |
| CLEARLY SPECIFY WHERE IS THIS ANCHOR GOING TO BE |
| MOUNTED TO AND PROVIDE PROOF THAT IT IS 3.000 PSI |
| CONCRETE. OTHERWISE, REVISE INSTALLATION SCHEDULE AS |
| REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| C) THE FASTENER EDGE DISTANCE EXCLUDES THE STUCCO |
| FINISH. SEE NOTES ON ANCHOR SCHEDULE TABLE ON SHEET 11 |
| OF 13. ADD THE STUCCO THICKNESS AND REVISE INSTALLATION |
| SCHEDULE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM |
| EMBEDMENT REQUIRED ON ANCHOR SCHEDULE TABLE ON SHEET 11 |
| OF 13. SEC. 107.2.1 CITY AMENDMENTS. |
| |