2018-02-01 11:52:08 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- WIND LOAD CALCULATIONS SUBMITTED: |
| A) NEED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| B) REVISE THE MINIMUM EDGE DISTANCE. ACCORDING TO |
| FOOTNOTE OF FIGURE R301.2(7) FBC-RESIDENTIAL, 6TH |
| EDITION (2017) THE MINIMUM EDGE DISTANCE "A" IS 4'-0" |
| IN ALL CASES NOT 3'-0". REVISE AS REQUIRED. |
| |
| 2- REVISE INSTALLATION SCHEDULE SUBMITTED. |
| A) OPENING #2 SPECIFY ANCHOR TYPE "A" WITH A SPACING OF |
| 14" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR SCHEDULE |
| TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS SUBMITTED |
| THIS ANCHOR REQUIRES 3.000PSI CONCRETE STRENGTH. IT |
| LOOKS LIKE THE BUILD OUT TRACK IS GOING TO BE MOUNTED |
| ON THE EDGE OF THE CONCRETE SLAB. TYPICALLY THE |
| CONCRETE SLABS FOR RESIDENTIAL PROJECTS ARE DESIGNED |
| FOR 2500PSI CONCRETE STRENGTH. REVISE THE ANCHOR TYPE |
| AND SPACING OR PROVIDE PROOF THAT THE CONCRETE STRENGTH |
| IS 3.000PSI. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| B) INSTALLATION SCHEDULE IS MISSING THE EDGE DISTANCE |
| DIMENSION. PROVIDE THE EDGE DISTANCE DIMENSION. NOTE: |
| THE FASTENER EDGE DISTANCE EXCLUDES THE STUCCO FINISH. |
| SEE NOTES ON ANCHOR SCHEDULE TABLE ON SHEET 11 OF 13. |
| ADD THE STUCCO THICKNESS TO THE EDGE DISTANCE ON THE |
| INSTALLATION SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM |
| EMBEDMENT REQUIRED ON ANCHOR SCHEDULE TABLE ON SHEET 11 |
| OF 13. SEC. 107.2.1 CITY AMENDMENTS. |
| |