2018-01-31 12:06:26RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- WIND LOAD CALCULATIONS SUBMITTED:
 A) NEED TO HAVE THE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 B) REVISE THE MINIMUM EDGE DISTANCE. ACCORDING TO
 FOOTNOTE OF FIGURE R301.2(7) FBC-RESIDENTIAL, 6TH
 EDITION (2017) THE MINIMUM EDGE DISTANCE "A" IS 4'-0"
 IN ALL CASES NOT 3'-0". REVISE AS REQUIRED.
  
 2- STORM PANELS FLORIDA PRODUCT APPROVAL FL11968-R4
 SUBMITTED;
 A) THE MINIMUM PANEL LENGTH IS 3'-0". SEE NOTE BELOW
 THE MAXIMUM DESIGN PRESSURES AND MAXIMUM PANEL LENGTH
 TABLE. OPENINGS # 5 AND #13 DON'T COMPLY WITH THIS
 REQUIREMENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) THE FASTENER EDGE DISTANCE SPECIFIED ON THE SHUTTERS
 INSTALLATION SCHEDULE DOESN'T MATCH FASTENER SPACING
 SHOWN ON ALTERNATIVE DETAIL 1 ON SHEET 11 OF 14 OF
 SHUTTER DRAWINGS SUBMITTED. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) TYPE OF TRACK SHOWN ON ALTERNATIVE DETAIL #4 ON
 SHEET 11 OF 14 DOESN'T MATCH THE TYPE OF TRACK MARKED
 ON SHEET 1A OF 14. REVISE AS REQUIRED TO MATCH AND
 AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WHY OPENING #12 IS NOT INCLUDED AT THE TOP
 AND BOTTOM OF ALTERNATIVES #1 AND #4 ON SHEET 11 OF 14.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 E) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM
 EMBEDMENT REQUIRED ON SHEET 11 OF 14. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 F) OPENINGS #1 AND #2 ARE LOCATED IN THE END ZONE #5.
 COORDINATE WITH ITEM #1(B) ABOVE. REVISE AS REQUIRED,
 INCLUDING THE DESIGN PRESSURES. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- ACCORDION SHUTTERS OPENING #20. REVISE INSTALLATION
 SCHEDULE SUBMITTED:
 A) SPECIFICATIONS FOR TOP OF OPENING #20 ON SHEET 4 OF
 13 IS FOR CONCRETE CONSTRUCTION. THIS IS A WOOD FRAMED
 HOUSE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) OPENINGS #20 SPECIFY ANCHOR TYPE "A" WITH A SPACING
 OF 16" O.C. AT THE BOTTOM. ACCORDING TO ANCHOR SCHEDULE
 TABLE ON PAGE 11 OF 13 OF ACCORDION SHUTTERS SUBMITTED
 THIS ANCHOR REQUIRES 3.000PSI CONCRETE STRENGTH. IT
 LOOKS LIKE THE FLOOR TRACK IS GOING TO BE MOUNTED ON
 THE CONCRETE SLAB. TYPICALLY THE CONCRETE SLABS FOR
 RESIDENTIAL PROJECTS ARE DESIGNED FOR 2500PSI CONCRETE
 STRENGTH. REVISE THE ANCHOR TYPE AND SPACING OR PROVIDE
 PROOF THAT THE CONCRETE STRENGTH IS 3.000PSI. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 C) THE FASTENER EDGE DISTANCE EXCLUDES THE STUCCO
 FINISH. SEE NOTES ON ANCHOR SCHEDULE TABLE ON SHEET 11
 OF 13. ADD THE STUCCO THICKNESS AND REVISE INSTALLATION
 SCHEDULE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) SPECIFY LENGTH OF ANCHORS TO VERIFY MINIMUM
 EMBEDMENT REQUIRED ON ANCHOR SCHEDULE TABLE ON SHEET 11
 OF 13. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- SCOPE OF WORK SHOWN ON THE PERMIT APPLICATION
 DOESN'T MATCH T INFORMATION SUBMITTED. PERMIT
 APPLICATION SPECIFIES INSTALLATION OF 23 ACCORDION
 SHUTTERS, WHILE INFORMATION SUBMITTED IS FOR
 INSTALLATION OF ACCORDION SHUTTERS ON ONLY ONE OPENING
 AND INSTALLATION OF STORM PANELS ON 19 OPENINGS. REVISE
 SCOPE OF WORK ON THE PERMIT APPLICATION TO MATCH ACTUAL
 SCOPE OF WORK TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  