Plan Review Notes
Plan Review Notes For Permit 18011050
Permit Number 18011050
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-02 11:37:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FLAME SPREAD RESISTANT REPORT PER ASTM E-84
 FOR PROPOSED CANOPY FABRIC.
 2. PROVIDE STATEMENMT THAT PLANS SHALL COMPLY WITH THE
 CITY OF WEST PALM BEACH MUNICIPAL CODE, ARTICLE VII,
 SECTION 18-282, PARA. (C), # (8).
 3. PROVIDE DESIGN WIND LOADS FOR PROPOSED EQUIPMENT PER
 FBC CHPT. 16.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 CITY OF WPB MUNI CODE
 ARTICLE VII
  
 SEC. 18-282. - DUTIES AND POWERS OF THE FLOODPLAIN
 ADMINISTRATOR.
 (A)
 DESIGNATION . THE BUILDING OFFICIAL IS DESIGNATED AS
 THE FLOODPLAIN ADMINISTRATOR. THE FLOODPLAIN
 ADMINISTRATOR MAY DELEGATE PERFORMANCE OF CERTAIN
 DUTIES TO OTHER EMPLOYEES.
 (B)
 GENERAL . THE FLOODPLAIN ADMINISTRATOR IS AUTHORIZED
 AND DIRECTED TO ADMINISTER AND ENFORCE THE PROVISIONS
 OF THIS ARTICLE. THE FLOODPLAIN ADMINISTRATOR SHALL
 HAVE THE AUTHORITY TO RENDER INTERPRETATIONS OF THIS
 ARTICLE CONSISTENT WITH THE INTENT AND PURPOSE OF THIS
 ARTICLE AND MAY ESTABLISH POLICIES AND PROCEDURES IN
 ORDER TO CLARIFY THE APPLICATION OF ITS PROVISIONS.
 SUCH INTERPRETATIONS, POLICIES, AND PROCEDURES SHALL
 NOT HAVE THE EFFECT OF WAIVING REQUIREMENTS
 SPECIFICALLY PROVIDED IN THIS ARTICLE WITHOUT THE
 GRANTING OF A VARIANCE PURSUANT TO SECTION 18-286 OF
 THIS ARTICLE.
 (C)
 APPLICATIONS AND PERMITS . THE FLOODPLAIN
 ADMINISTRATOR, IN COORDINATION WITH OTHER PERTINENT
 OFFICES OF THE CITY, SHALL:
 (1)
 REVIEW APPLICATIONS AND PLANS TO DETERMINE WHETHER
 PROPOSED NEW DEVELOPMENT WILL BE LOCATED IN FLOOD
 HAZARD AREAS;
 (2)
 REVIEW APPLICATIONS FOR MODIFICATION OF ANY EXISTING
 DEVELOPMENT IN FLOOD HAZARD AREAS FOR COMPLIANCE WITH
 THE REQUIREMENTS OF THIS ARTICLE;
 (3)
 INTERPRET FLOOD HAZARD AREA BOUNDARIES WHERE SUCH
 INTERPRETATION IS NECESSARY TO DETERMINE THE EXACT
 LOCATION OF BOUNDARIES; A PERSON CONTESTING THE
 DETERMINATION SHALL HAVE THE OPPORTUNITY TO APPEAL THE
 INTERPRETATION;
 (4)
 PROVIDE AVAILABLE FLOOD ELEVATION AND FLOOD HAZARD
 INFORMATION;
 (5)
 DETERMINE WHETHER ADDITIONAL FLOOD HAZARD DATA SHALL BE
 OBTAINED FROM OTHER SOURCES OR SHALL BE DEVELOPED BY AN
 APPLICANT;
 (6)
 REVIEW APPLICATIONS TO DETERMINE WHETHER PROPOSED
 DEVELOPMENT WILL BE REASONABLY SAFE FROM FLOODING;
 (7)
 ISSUE FLOODPLAIN DEVELOPMENT PERMITS OR APPROVALS FOR
 DEVELOPMENT OTHER THAN BUILDINGS AND STRUCTURES THAT
 ARE SUBJECT TO THE FLORIDA BUILDING CODE, INCLUDING
 BUILDINGS, STRUCTURES AND FACILITIES EXEMPT FROM THE
 FLORIDA BUILDING CODE, WHEN COMPLIANCE WITH THIS
 ARTICLE IS DEMONSTRATED, OR DISAPPROVE THE SAME IN THE
 EVENT OF NONCOMPLIANCE; AND
 (8)
 COORDINATE WITH AND PROVIDE COMMENTS TO THE BUILDING
 OFFICIAL TO ASSURE THAT APPLICATIONS, PLAN REVIEWS, AND
 INSPECTIONS FOR BUILDINGS AND STRUCTURES IN FLOOD
 HAZARD AREAS COMPLY WITH THE APPLICABLE PROVISIONS OF
 THIS ARTICLE.
  
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  
  
  
  
  