Plan Review Notes
Plan Review Notes For Permit 18011037
Permit Number 18011037
Review Stop G
Sequence Number 1
Notes
Date Text
2018-02-20 14:01:26DENIED
  
 1) GENERAC COMPLIES WITH THE NFPA (37) SEC 4.1.4 AND
 HAS CHANGED GUIDELINES FOR INSTALLATION OF THE
 GENERATOR YOU ARE INSTALLING TO 18 INCHES FROM THE BACK
 SIDE OF THE GENERATOR TO A STATIONARY WALL OR BUILDING
 AND NO WINDOWS OR OPENING IN THE WALL ARE PERMITTED
 WITHIN 5 FEET FROM ANY POINT OF THE GENERATOR. THE
 SPECIFICATION FOR THE MANUAL YOU SUMMITED IS FROM
 12/4/15 AND IT IS OUTDATED, PLEASE SUBMIT THE UPDATED
 ONES FROM 9/15/17 WHICH HAVE THE ABOVE CLEARANCES
 SPECIFIED. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2) THE APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 ARE NOT THE 2017 FBC FG CODE, PLEASE PROVIDE UPDATED
 SHEETS TO REFLECT THE WORK BEING DONE. WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  