Plan Review Notes For Permit 18010970 |
Permit Number |
18010970 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-01-30 09:05:48 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 4) ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|