Date |
Text |
2018-02-02 10:00:56 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- EXTERIOR DOORS DRAWING NO JW142012FL SUBMITTED: |
| A) THESE DOORS DON'T MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ENGINEER OF RECORD. NEED TO PROVIDE |
| PRODUCT APPROVAL (2 COPIES) OF DOORS THAT MEETS THE |
| DESIGN PRESSURES CALCULATED BY THE ENGINEER ON SHEET |
| A-1/3. |
| SEC. R301.1 FB-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| CORRESPONDS TO DRAWING JW142012FL SUBMITTED. |
| FAC 61G20-3.001 |
| |
| 2- CASEMENT WINDOWS NOA 14-0908.20 SUBMITTED: CLEARLY |
| MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING TO BE |
| INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET |
| A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 3- SINGLE HUNG WINDOWS NOA 16-1003.01 SUBMITTED: |
| CLEARLY MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING |
| TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET |
| A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 4- FIXED WINDOWS NOA 17-0531.05 SUBMITTED: |
| A) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR FIXED |
| WINDOWS IF PLANS DON'T SPECIFY ANY FIXED WINDOWS. IF |
| FIXED WINDOWS ARE GOING TO BE INSTALLED, THEN ENGINEER |
| OF RECORD NEEDS TO REVISE PLANS ACCORDINGLY. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| B) IF INSTALLING FIXED WINDOWS, THEN CLEARLY MARK WHICH |
| WINDOW SIZE AND GLASS TYPE IS GOING TO BE INSTALLED TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED |
| BY THE ENGINEER OF RECORD ON SHEET A-1/3. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 6- NEED TO PROVIDE WINDOW MULLIONS PRODUCT APPROVALS (2 |
| COPIES) AS REQUESTED ON PROVISO. NOTE: CLEARLY SPECIFY |
| WINDOW SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH |
| THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF |
| RECORD ON SHEET A-1/3. SEC. R301.1 FBC-RESIDENTIAL. |
| |