2018-02-02 10:00:56RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EXTERIOR DOORS DRAWING NO JW142012FL SUBMITTED:
 A) THESE DOORS DON'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. NEED TO PROVIDE
 PRODUCT APPROVAL (2 COPIES) OF DOORS THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER ON SHEET
 A-1/3.
 SEC. R301.1 FB-RESIDENTIAL, 5TH EDITION (2014).
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO DRAWING JW142012FL SUBMITTED.
 FAC 61G20-3.001
  
 2- CASEMENT WINDOWS NOA 14-0908.20 SUBMITTED: CLEARLY
 MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET
 A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- SINGLE HUNG WINDOWS NOA 16-1003.01 SUBMITTED:
 CLEARLY MARK WHICH WINDOW SIZE AND GLASS TYPE IS GOING
 TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD ON SHEET
 A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  
 4- FIXED WINDOWS NOA 17-0531.05 SUBMITTED:
 A) CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR FIXED
 WINDOWS IF PLANS DON'T SPECIFY ANY FIXED WINDOWS. IF
 FIXED WINDOWS ARE GOING TO BE INSTALLED, THEN ENGINEER
 OF RECORD NEEDS TO REVISE PLANS ACCORDINGLY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) IF INSTALLING FIXED WINDOWS, THEN CLEARLY MARK WHICH
 WINDOW SIZE AND GLASS TYPE IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD ON SHEET A-1/3. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- NEED TO PROVIDE WINDOW MULLIONS PRODUCT APPROVALS (2
 COPIES) AS REQUESTED ON PROVISO. NOTE: CLEARLY SPECIFY
 WINDOW SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET A-1/3. SEC. R301.1 FBC-RESIDENTIAL.
  