2018-01-24 14:21:06RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- REPLACEMENT OF BEDROOM WINDOWS EGRESS REQUIREMENTS:
 A) SKETCH SUBMITTED INDICATES THAT THE OPENING WHERE
 THE WINDOWS ARE GOING TO BE REPLACED IS LOCATED IN AN
 "OFFICE". ACCORDING TO CITY RECORDS THIS ROOM WAS
 DESIGNED AS BEDROOM #2. (MODEL "C" PERMIT #91BN02294).
 PLEASE REVISE INFORMATION ON SKETCH TO AVOID CONFLICTS.
 INDICATE THAT IS A BEDROOM. THIS ROOM MAY BE USED AS AN
 OFFICE, BUT IT NEEDS TO COMPLY WITH THE BEDROOM EGRESS
 REQUIREMENTS OF SEC. R702.5 FBC-EXISTING BUILDING, 6TH
 EDITION (2017).
  
 B) SPECIFY ACTUAL SIZE OF EXISTING 2-25 SINGLE HUNG
 WINDOWS AND SIZE OF ROUGH OPENING TO VERIFY COMPLIANCE
 WITH THE PROPOSED DOUBLE HUNG WINDOWS AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING. PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE PROPOSED
 DOUBLE HUNG WINDOW (36" X 61-1/2") WILL PROVIDE AN
 EQUAL OR GREATER WINDOW OPENING AREA THAN THE EXISTING
 2-25SH WINDOWS AS REQUIRED BY R702.5 FBC-EXISTING
 BUILDING, 6TH EDITION (2017).
  
 2- WINDOW MULLION PRODUCT APPROVAL FL7472-R2 SUBMITTED:
 A) THIS PRODUCT APPROVAL IS NOT APPROVED. THE STATUS OF
 THE PRODUCT APPROVAL SUBMITTED IS "VALIDATED". PROVIDE
 2 COPIES OF PRODUCT APPROVAL THAT IS "APPROVED" UNDER
 THE CURRENT 2017 FBC.
 FAC 61G20-3.001.
  
 B) CLEARLY SPECIFY SIZED OF ALL WINDOW MULLIONS TO BE
 USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
 SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION (2017).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]