2018-01-24 14:21:06 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: FBC 6TH EDITION (2017). |
| |
| 1- REPLACEMENT OF BEDROOM WINDOWS EGRESS REQUIREMENTS: |
| A) SKETCH SUBMITTED INDICATES THAT THE OPENING WHERE |
| THE WINDOWS ARE GOING TO BE REPLACED IS LOCATED IN AN |
| "OFFICE". ACCORDING TO CITY RECORDS THIS ROOM WAS |
| DESIGNED AS BEDROOM #2. (MODEL "C" PERMIT #91BN02294). |
| PLEASE REVISE INFORMATION ON SKETCH TO AVOID CONFLICTS. |
| INDICATE THAT IS A BEDROOM. THIS ROOM MAY BE USED AS AN |
| OFFICE, BUT IT NEEDS TO COMPLY WITH THE BEDROOM EGRESS |
| REQUIREMENTS OF SEC. R702.5 FBC-EXISTING BUILDING, 6TH |
| EDITION (2017). |
| |
| B) SPECIFY ACTUAL SIZE OF EXISTING 2-25 SINGLE HUNG |
| WINDOWS AND SIZE OF ROUGH OPENING TO VERIFY COMPLIANCE |
| WITH THE PROPOSED DOUBLE HUNG WINDOWS AS REQUIRED BY |
| SEC. 702.5 FBC-EXISTING BUILDING. PROVIDE |
| MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE PROPOSED |
| DOUBLE HUNG WINDOW (36" X 61-1/2") WILL PROVIDE AN |
| EQUAL OR GREATER WINDOW OPENING AREA THAN THE EXISTING |
| 2-25SH WINDOWS AS REQUIRED BY R702.5 FBC-EXISTING |
| BUILDING, 6TH EDITION (2017). |
| |
| 2- WINDOW MULLION PRODUCT APPROVAL FL7472-R2 SUBMITTED: |
| A) THIS PRODUCT APPROVAL IS NOT APPROVED. THE STATUS OF |
| THE PRODUCT APPROVAL SUBMITTED IS "VALIDATED". PROVIDE |
| 2 COPIES OF PRODUCT APPROVAL THAT IS "APPROVED" UNDER |
| THE CURRENT 2017 FBC. |
| FAC 61G20-3.001. |
| |
| B) CLEARLY SPECIFY SIZED OF ALL WINDOW MULLIONS TO BE |
| USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. |
| SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION (2017). |
| |