Plan Review Notes For Permit 18010778 |
Permit Number |
18010778 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-02-16 18:16:56 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW | | CHECKLIST. | | CODE: FBC 6TH EDITION (2017). | | | | 1- STORM SHUTTERS INSTALLATION SCHEDULE IS NOT CLEAR. | | SPECIFY SHUTTER MOUNTING CONDITIONS. MIAMI DADE IS NOT | | A MOUNTING CONDITION. SHUTTERS GLASS SEPARATION NEEDS | | TO BE REVISED. SEE TABLE 2 ON SHEET 5 OF 5 OF NOA | | DRAWINGS SUBMITTED. THE SHUTTERS SPAN DIMENSION IS NOT | | CLEAR IF THE STORM PANELS ARE MOUNTED VERTICALLY. | | REVISE ANCHOR SPACING BASED ON THE SUBSTRATE TO RECEIVE | | THE SHUTTERS (CONCRETE BLOCK). SEC. 107.2.1 CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|