2018-02-16 18:16:56RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- STORM SHUTTERS INSTALLATION SCHEDULE IS NOT CLEAR.
 SPECIFY SHUTTER MOUNTING CONDITIONS. MIAMI DADE IS NOT
 A MOUNTING CONDITION. SHUTTERS GLASS SEPARATION NEEDS
 TO BE REVISED. SEE TABLE 2 ON SHEET 5 OF 5 OF NOA
 DRAWINGS SUBMITTED. THE SHUTTERS SPAN DIMENSION IS NOT
 CLEAR IF THE STORM PANELS ARE MOUNTED VERTICALLY.
 REVISE ANCHOR SPACING BASED ON THE SUBSTRATE TO RECEIVE
 THE SHUTTERS (CONCRETE BLOCK). SEC. 107.2.1 CITY
 AMENDMENTS.
  