2018-01-23 18:28:24 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE; FBC 6TH EDITION (2017). |
| |
| 1- FLOOR PLAN SKETCH SUBMITTED: |
| A) CLEARLY IDENTIFY ALL BEDROOMS OR SLEEPING AREAS TO |
| VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| 702.5 FBC-EXISTING BUILDING, 6TH EDITION (2017). |
| |
| B) CLEARLY SPECIFY EXISTING WINDOW TYPE AND SIZE AND |
| PROPOSED WINDOW TYPE AND SIZE TO VERIFY COMPLIANCE WITH |
| THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| BUILDING. NOTE: INCLUDE THE WINDOW ROUGH OPENING. |
| |
| 2- PROVIDE WINDOW CURRENT PRODUCT APPROVAL. NOA |
| 14-0722.07 SUBMITTED EXPIRED ON NOVEMBER 14, 2017. |
| FAC 61G203.001. |
| |
| 3- STORM SHUTTERS NOA 17-0118.08 SUBMITTED; |
| A) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE OR PROVIDE COMPLETE INSTALLATION IN ANY OTHER |
| FORMAT THAT WILL HAVE ALL THE REQUIRED INFORMATION TO |
| VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC. |
| R301.1 FBC-RESIDENTIAL, 6TH EDITION (2017). |
| |
| B) PROVIDE COMPLETE DRAWINGS. DRAWINGS SUBMITTED ARE |
| CUT AND MISSING PAGES. PROVIDE COMPLETE DRAWINGS THAT |
| ARE PRINTED ON THE SAME PAGE. PRINT ON LANDSCAPE FORMAT |
| SO DRAWINGS ARE LEGIBLE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- PROVIDE WINDOW MULLION PRODUCT APPROVAL AS REQUIRED |
| BY FAC 61G20-3.001 AND CLEARLY IDENTIFY MULLIONS SIZE |
| TO BE USED TO VERIFY COMPLIANCE WITH SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| 109.3 CITY AMENDMENTS. |
| REVISE VALUATION AS REQUIRED. |
| |
| 6- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13 |
| F.S. |
| |