Plan Review Notes
Plan Review Notes For Permit 18010743
Permit Number 18010743
Review Stop M
Sequence Number 2
Notes
Date Text
2018-03-05 10:20:402ND REVIEW FBC-2017 RESIDENTIAL MECHANICAL, WEST PALM
 BEACH AMENDMENTS TO THE FBC
 PERMIT #18010743
 1/30/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) 2ND REQUEST FOR THE AC CONTRACTOR TO PROVIDE HIS/HER
 SIGNATURE ON THE PLAN- SECTION 107.2.1
  
 2) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGYGAUGE
 FORM R405-2017.
  
 3) INDICATE HOW ACCESS TO THE AIR HANDLER IN THE ATTIC
 WILL BE PROVIDED- PLEASE SEE SECTION R403.3.3.6 FBC-17
 ENERGY CONSERVATION.
  
 4) THE 8" TRANSFER DUCT FROM THE MASTER BEDROOM IS
 UNDERSIZED PER SECTION M1602.3 FBC-17 RESIDIENTIAL.
  
 5) SHOW THE LOCATION OF THE NNEW AC CONDENSER ON THE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  