2018-01-30 10:44:55 | 1ST REVIEW FBC-2017 MECHANICAL, WEST PALM BEACH |
| AMENDMENTS TO THE FBC |
| PERMIT #18010743 |
| 1/30/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC PLAN IS UNACCEPTABLE BECAUSE IT IS NOT |
| LEGIBLE AND IS NOT DRAWN TO A MINIMUM 1/8" SCALE.- |
| SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. PLEASE |
| PROVIDE A CLEAR LEGIBLE PLAN WITH ALL ROOMS AND SPACES |
| IDENTIFIED. |
| |
| 2) THE PLAN MUST BEAR THE NAME AND SIGNATURE OF THE |
| CONTRACTOR WHO PREPARED THE DESIGN- SECTION 107.2.1 |
| |
| 3) THE PROJECT IS NOT AN "AC CHANGEOUT". THIS IS A NEW |
| AC AND DUCTWORK INSTALLATION. PLEASE REMOVE THE |
| CHANGEOUT FORM FROM THE FILE AND PROVIDE AN EQUIPMENT |
| SCHEDULE ON THE PLAN THAT LISTS THE MAKE AND MODEL OF |
| THE SYTEM, THE COOLING AND |
| |
| HEATING CAPACITIES, THE TOTAL SUPPLY CFMS, THE |
| EFFICENCY RATING, AND ELECTRICAL DATA. |
| |
| 4) PROVIDE THE SUPPLY CFMS AT EACH DIFFUSER LOCATION. |
| |
| 5) THE COOLING AND HEATING EQUIPMENT SUMMARIES ON THE |
| AC CALCULATIONS WERE LEFT BLANK. PLEASE PROVIDE THE |
| REQUIRED INFORMATION- SECTION R403.7.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 6) THE ENERGY FORM R405-2014 IS OUTDATED. THE FBC-17 |
| ENERGY CONSERVATION CODE TOOK EFFECT ON 1/1/18. PLEASE |
| NOTE THE OWNER/AGENT MUST SIGN AND DATE THE FORM |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |