2018-01-26 06:02:571) THE GAS CODE IN EFFECT FOR THIS PERMIT IS THE 2017
 FBC-FUEL GAS, NOT THE 2014 AS NOTED ON THE PLANS AND
 THE SUBMITTED SIZING TABLES.
 2) THE MANUFACTURER'S SPECIFICATIONS FOR THE 22 KW
 GENERATOR SHOW THE BTU RATING OF THE THE GENERATOR AT
 100 % FULL LOAD 310,000 BTU'S BUT THE GAS PLAN SHOWS
 281,000 BTU'S. CLARIFY.SEE 2017 FBC-FUEL GAS SECS.
 402.1, 402.2.
 3) THE SIZE OF THE GAS LINE FROM THE OUTLET OF THE GAS
 METER SHALL BE INCREASED TO 1 1/4 INCH PER 2017
 FBC-FUEL GAS TABLE 402.4 (2). THE MAXIMUM BTU LOAD THAT
 CAN BE INSTALLED ON A 1/2 LB. GAS METER WITH A 1 INCH
 LINE WITH A DISTANCE OF 45 FEET IS 284,000 BTU'S. THE
 TOTAL BTU LOAD MUST BE TAKEN INTO ACCOUNT FOR THE
 SIZING OF THE PIPE LINE AT THE OUTLET OF THE
 METER.REFER TO 2017 FBC-FUEL GAS SECS.401.3, 401.4,
 401.8.
 4) THE GAS PLAN REFERENCES TABLE 402.4 (15) WHICH IS
 FOR CSST BUT THERE IS NO CSST SHOWN ON THE GAS PLAN.
 CLARIFY.
 5) IDENTIFY THE TYPE OF PIPE RUNNING THROUGH THE
 GARAGE. IF IT IS CSST, SUBMIT THE CORRESPONDING EHD OF
 THE SIZE CSST PIPE IN ACCORDANCE WITH TABLE 402.4 (15)
 OF THE 2017 FBC-FUEL GAS CODE.
  