2018-01-22 12:19:49RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- ENGINEER LETTER SUBMITTED FOR THE ROOF TO WALL
 CONNECTIONS NEED TO BE REVISED. ACCORDING TO SEC.
 R301.2.1.4 FBC-RESIDENTIAL 5TH EDITION (2014) THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE AS REQUIRED OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS.
  
 2- ROOF TILE ADHESIVE PRODUCT APPROVAL FL6332-R8
 SUBMITTED: CLEARLY MARK ON THE PRODUCT APPROVAL THE
 PADDY SIZE TO BE INSTALLED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND THAT THIS BUILDING IS LOCATED IN
 EXPOSURE "D". COORDINATE WITH ITEM #1 ABOVE.
  
 3- PROVIDE SKYLIGHT CURRENT PRODUCT APPROVAL. PRODUCT
 APPROVAL FL2418-R9 SUBMITTED IS FOR THE 2014 CODE. THE
 CURRENT CODE IS THE FBC-6TH EDITION (2017). PROVIDE 2
 COPIES OF CURRENT PRODUCT APPROVAL. FAC 61G20-3.001.
  