Plan Review Notes For Permit 18010605 |
Permit Number |
18010605 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-02-08 06:58:59 | 02/08/2018 2ND PLUMBING REVIEW**DENIED** | | | | 1) THE INLET SIZE OF THE INTERCEPTOR IS UNDERSIZED AND | | SHALL BE 3? FBC-P 710.1(2) AS YOU NOW HAVE 8 DFU ON A | | 2? LINE. THE SIZING OF THE ACTUAL DRAIN PIPING IS ALSO | | UNDERSIZED. | | | | 2) SHOW THE DEVELOP PIPING LENGTH OF EACH SECTION OF | | PIPING. FBC 107.2.1 | | | | 3) THE NEW FLOOR PLAN NOW SHOWS A HAND SINK. 2-COPIES | | ARE REQUIRED AND THE FOLLOWING COMMENTS WILL NEED TO BE | | ADDRESSED. FBC-P 107.2.1 | | | | A) THE HAND SINK IS REQUIRED TO BE TRAPPED AND VENTED | | FBC-P 1002.1 | | | | B) THE HAND SINK MUST BE INCLUDED IN YOUR GREASE | | INTERCEPTOR SIZING CALCULATION. FBC 107.2.1 | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | | | |
|