Plan Review Notes
Plan Review Notes For Permit 18010605
Permit Number 18010605
Review Stop P
Sequence Number 2
Notes
Date Text
2018-02-08 06:58:5902/08/2018 2ND PLUMBING REVIEW**DENIED**
  
 1) THE INLET SIZE OF THE INTERCEPTOR IS UNDERSIZED AND
 SHALL BE 3? FBC-P 710.1(2) AS YOU NOW HAVE 8 DFU ON A
 2? LINE. THE SIZING OF THE ACTUAL DRAIN PIPING IS ALSO
 UNDERSIZED.
  
 2) SHOW THE DEVELOP PIPING LENGTH OF EACH SECTION OF
 PIPING. FBC 107.2.1
  
 3) THE NEW FLOOR PLAN NOW SHOWS A HAND SINK. 2-COPIES
 ARE REQUIRED AND THE FOLLOWING COMMENTS WILL NEED TO BE
 ADDRESSED. FBC-P 107.2.1
  
 A) THE HAND SINK IS REQUIRED TO BE TRAPPED AND VENTED
 FBC-P 1002.1
  
 B) THE HAND SINK MUST BE INCLUDED IN YOUR GREASE
 INTERCEPTOR SIZING CALCULATION. FBC 107.2.1
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  