2018-02-27 16:54:17 | DENIED |
| |
| 1. THE NOTE ON SHOWER INSTALLATION REFERS TO 2014 |
| FLORIDA BUILDING CODE RESIDENTIAL PLUMBING CODE, PLEASE |
| MAKE REFERENCES TO 2017 FLORIDA BUILDING CODE PLUMBING |
| SECTION 417 AND NOTE THE CORRECT COMPLIANCE FBC WPB A |
| 107.1 GENERAL PLAN APPLICATION. |
| 2. WHEN CHANGING TUB TO THE SHOWER WILL THERE BE A |
| VALVE REPLACEMENT AND IF SO IT MUST COMPLY WITH 2017 |
| FBC P SECTION 424.3. PLEASE PROVIDE A SPECIFICATION FOR |
| SHOWER VALVE TYPE THAT COMPLIES. WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 3. REFRIGERATOR MUST BE EQUIPPED WITH HAMMER ARRESTOR |
| 2017 FBC P 604.9. |
| 4. SHOWER MEASUREMENT IS AT 30" PLUS 4" THAT MAKE THE |
| TOILET IS 26", REFER TO 2017 FBC P 405.3.1 THAT STATE A |
| WATER CLOSET, URINAL, LAVATORY OR BIDET SHALL NOT BE |
| SET CLOSER THAN 15 INCHES FROM ITS CENTER TO ANY SIDE |
| WALL, PARTITION, VANITY OR OTHER OBSTRUCTION, OR CLOSER |
| THAN 30 INCHES CENTER TO CENTER BETWEEN ADJACENT |
| FIXTURES. THE SHOWER MAY BE SMALLER AS LONG AS IT |
| COMPLIES WITH FBC P 417.4. SHOWER COMPARTMENT SHALL NOT |
| BE LESS THAN 900 SQUARE INCHES. SHOWER WASTE OUTLET |
| SHALL WITH FBC P 417.3, PLEASE PROVIDE SHOWER DRAIN |
| DETAILS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 5. SHOWER LINING SHALL COMPLY WITH FBC P 417.2 LINERS |
| SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD |
| THE FIXTURE DRAINS AND BE SECURELY FASTENED TO THE |
| WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A |
| WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET. |
| 6. A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |