2018-02-20 15:52:29 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE | | CURRENT CODES ABOVE) | | 2. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE | | DESIGN PROFESSIONAL OF RECORD. FS 471.003(2)(H); | | 471.025; FBC 107.2.1 | | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|