2018-01-25 07:58:45 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18010553 |
| ADD: 5600 N. FLAGLER DR. SUITE: 1009 |
| CONT: COLORS GROUP INC. |
| TEL: 561-262-6303 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. JAN. 25/ 2018 |
| ACTION: DENIED |
| |
| 1) THE DESIGN PROFESSIONAL HAS DESIGNED THE PLANS TO |
| THE WRONG CODE AND EDITION OF THE CODE. THE PLANS STATE |
| THEY WERE DESIGNED TO THE 2014 FBC-RESIDENTIAL CODE. |
| EFFECTIVE DEC. 31/2017 THE 6TH EDITION/ 2017 FLORIDA |
| BUILDING CODE WAS ADOPTED STATEWIDE. PLEASE UPDATE |
| PLANS. THIS IS A HIGHRISE BUILDING MULTI-UNIT R-2 |
| OCCUPANCY, NOT A SINGLE FAMILY RESIDENCE. |
| |
| 2) THE WIND DESIGN REVERTS BACK TO THE 2010 FBC AND A |
| EXPOSURE C, WE ARE UNDER THE 2017 FBC-B STILL ASCE |
| 7-10, EXPOSURE D. THIS CONDOMINIUM IS DIRECTLY ON THE |
| INTERCOASTAL WATERWAY. |
| |
| 3) THE DESIGNER OF RECORD HAS NOT LISTED HOW THE PLANS |
| WERE DESIGNED UNDER THE 2017 EXISTING BUILDING CODE ALL |
| EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS |
| LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED |
| BY THE APPLICANT. |
| 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD. |
| 301.1.2 WORK AREA COMPLIANCE METHOD. |
| 301.1.3 PERFORMANCE COMPLIANCE METHOD. |
| |
| 4) SHEET A-1 NOTE # 4 INDICATES THE REMOVAL OF A |
| PORTION OF THE DROP CEILING BUT NO INFORMATION IS GIVEN |
| HOW THE REMAINING PORTION OF THE DROPPED CEILING IS TO |
| BE FRAMED? TYPE OF FRAMING SUPPORTS, SIZE, SPACING, |
| SPAN, DEFLECTION LIMITS, ANCHORAGE TO THE CEILING |
| ABOVE, THICKNESS OF CEILING FINISH MATERIAL. |
| 2017 FBC-B TABLE 2506.2 STEEL STUDS NON-LOADING ASTM |
| C645. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |