Plan Review Notes
Plan Review Notes For Permit 18010553
Permit Number 18010553
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-25 07:58:452014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18010553
 ADD: 5600 N. FLAGLER DR. SUITE: 1009
 CONT: COLORS GROUP INC.
 TEL: 561-262-6303
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 25/ 2018
 ACTION: DENIED
  
 1) THE DESIGN PROFESSIONAL HAS DESIGNED THE PLANS TO
 THE WRONG CODE AND EDITION OF THE CODE. THE PLANS STATE
 THEY WERE DESIGNED TO THE 2014 FBC-RESIDENTIAL CODE.
 EFFECTIVE DEC. 31/2017 THE 6TH EDITION/ 2017 FLORIDA
 BUILDING CODE WAS ADOPTED STATEWIDE. PLEASE UPDATE
 PLANS. THIS IS A HIGHRISE BUILDING MULTI-UNIT R-2
 OCCUPANCY, NOT A SINGLE FAMILY RESIDENCE.
  
 2) THE WIND DESIGN REVERTS BACK TO THE 2010 FBC AND A
 EXPOSURE C, WE ARE UNDER THE 2017 FBC-B STILL ASCE
 7-10, EXPOSURE D. THIS CONDOMINIUM IS DIRECTLY ON THE
 INTERCOASTAL WATERWAY.
  
 3) THE DESIGNER OF RECORD HAS NOT LISTED HOW THE PLANS
 WERE DESIGNED UNDER THE 2017 EXISTING BUILDING CODE ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT.
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 4) SHEET A-1 NOTE # 4 INDICATES THE REMOVAL OF A
 PORTION OF THE DROP CEILING BUT NO INFORMATION IS GIVEN
 HOW THE REMAINING PORTION OF THE DROPPED CEILING IS TO
 BE FRAMED? TYPE OF FRAMING SUPPORTS, SIZE, SPACING,
 SPAN, DEFLECTION LIMITS, ANCHORAGE TO THE CEILING
 ABOVE, THICKNESS OF CEILING FINISH MATERIAL.
 2017 FBC-B TABLE 2506.2 STEEL STUDS NON-LOADING ASTM
 C645. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  