Plan Review Notes
Plan Review Notes For Permit 18010551
Permit Number 18010551
Review Stop E
Sequence Number 1
Notes
Date Text
2018-01-23 13:38:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE COPY OF PLAN PROVIDED. MUST PROVIDE 2
 COPIES OF PLAN, SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. FS 481.229; FBC 107.1, 107.2.1, 107.3.5
 2. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS.
 SMOKE ALARMS WITH 10 YEAR NON-REMOVABLE BATTERY IS
 ACCEPTACLE FOR LEVEL 1 ALTERATIONS. FBC R314.3, FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  