Plan Review Notes For Permit 18010523 |
Permit Number |
18010523 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-09 16:50:19 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | FAC 61G20-3.001 FOR: | | A) FLAT ROOF MODIFIED BITUMEN ROOF SYSTEM FLORIDA | | PRODUCT APPROVAL FL1654-R20 SUBMITTED: NEED PRODUCT | | APPROVAL FOR CURRENT 2017 CODE VERSION. AND, NEED TO | | SPECIFY WHICH APPROVED ASSEMBLY FROM PRODUCT APPROVAL | | SUBMITTED IS GOING TO BE INSTALLED. NOTE: IF SELECTED | | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF | | ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL | | BE REQUIRED. | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | |
|