2018-02-12 10:38:58 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| CURRENT CODE ABOVE) |
| 2. FEED FROM 150 AMP DISCONNECT TO INTERIOR PANEL IS |
| REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, |
| SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| E3704.6, 3607.3.1 |
| 3. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. FBC |
| 107.2.1; NEC 230.2; FBC RE E3601.2 |
| 4. PROVIDE COMPLETE RISER DIAGRAM FOR MAIN HOUSE AND |
| SECONDARY BUILDING, SHOWING ALL DETAILS OF SERVICE |
| EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND |
| BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). |
| SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING |
| TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, |
| 408.30; FBC RE E3706.1, E3608.1, E3609.3; FBC 107.2.1 |
| 5. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| 6. THE CURRENT AFCI NOTE DOES NOT INCLUDE ALL AREAS |
| REQUIRED TO HAVE AFCI PROTECTION. CODE STATES: ?BRANCH |
| CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED.? ALSO, THE PANEL SCHEDULE DOES |
| NOT REFLECT THESE REQUIREMENTS. PROVIDE CORRECTIONS. |
| NEC 210.12, 4080.4; FBC RE E3902.16 |
| 7. NOTE 9 STATES THAT RECEPTACLES SHALL BE TAMPER |
| RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| CORRECTION. NEC 406.12; FBC RE E4002.14 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |