Plan Review Notes
Plan Review Notes For Permit 18010523
Permit Number 18010523
Review Stop B
Sequence Number 1
Notes
Date Text
2018-02-07 17:41:42NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- ADDRESS SHOWN ON THE PERMIT APPLICATION AND IN ALL
 PLANS IS INCORRECT. REVISE THE ADDRESS NUMBER AND ZIP
 CODE. IT LOOKS LIKE THE CORRECT ADDRESS IS 979 39TH
 STREET. AND THE CORRECT ZIP CODE IS 33407 NOT 33470.
 NOTE: COORDINATE WITH ZONING. IT SEEMS TO BE MORE THAN
 ONE BUILDING IN THIS LOT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE SITE PLAN AND SURVEY SHOWING THE EXACT
 LOCATION OF THE PROPOSED HOUSE TO VERIFY COMPLIANCE
 WITH THE FIRE RESISTANCE CONSTRUCTION REQUIREMENTS OF
 SEC. R302 FBC-RESIDENTIAL, 6TH EDITION (2017).
  
 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
  
 5- AFTER DECEMBER 31ST, 2017 THE NEW CODE FBC 6TH
 EDITION (2017) WENT INTO EFFECT. ALL PERMIT
 APPLICATIONS AFTER JANUARY 1ST 2018 NEED TO BE ENFORCED
 UNDER THE 2017 CODE. PERMIT APPLICATION WAS SUBMITTED
 ON JANUARY 16TH 2018. NEED TO UPDATE ALL PLANS AND
 NOTES REFERENCING THE CURRENT CODE. REVISE THE
 APPLICABLE CODES, ALL TYPICAL STAIR & HANDRAIL NOTES
 AND ALL STRUCTURAL NOTES ON SHEET S.1 AS REQUIRED. SEC.
 553 FLORIDA STATUTES.
  
 6- CLARIFY DESIGN CRITERIA INFORMATION SHOWN ON SHEET
 S.1:
 A) LOADS SHOWN ARE NOT CLEAR. (1) WHAT DOES "R.DL"
 STANDS FOR?. THERE IS NO ABBREVIATION LEGEND TO FIGURE
 THIS OUT?. (2) THERE ARE TWO DIFFERENT LOADS SHOWN, BUT
 THEY DON'T ADD UP ON THE TOTAL LOAD?. FOR EXAMPLE "TOP
 CHORD DEAD" 15 AND 4.2. WHAT IS THIS?. (3) MISSING ALL
 THE LIVE AND DEAD LOADS FOR THE SECOND FLOOR. REVISE AS
 REQUIRED. CLEARLY IDENTIFY ALL THE DESIGN LOADS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B) CLARIFY WHAT DOES "TOP CHORD C.B. " AND "SHEETING BY
 BUILDER" STANDS FOR?. THIS IS NOT CLEAR. THIS IS NOT
 STANDARD DESIGN CRITERIA. AND THERE IS NOT ABBREVIATION
 LEGEND IDENTIFYING THIS. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) CLARIFY WHAT DOES "BOTTOM CHORD C.B. " AND "SHEETING
 BY BUILDER" STANDS FOR?. THIS IS NOT CLEAR. THIS IS NOT
 STANDARD DESIGN CRITERIA. AND THERE IS NOT ABBREVIATION
 LEGEND IDENTIFYING THIS. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WHAT DOES "BUILDING CATEGORY II: NON
 RESTRICTIVE" STANDS FOR?. WHAT SECTION OF THE CODE IS
 THIS INFORMATION TAKEN FROM?. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- REVISE THE SQUARE FOOTAGE SHOWN ON THE PROJECT DATA
 ON SHEET S.1: INCLUDE THE TOTAL ENTRY PORCH AREA AS
 WELL. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- ROOF DRAIN GUTTERS AND DOWNSPOUTS ARE REQUIRED. SEC.
 R318.5 FBC-RESIDENTIAL. DOWNSPOUTS NEED TO DISCHARGE AT
 LEAST ONE FOOT AWAY FROM THE STRUCTURE SIDEWALL. ROOF
 FRAMING PLAN AND EXTERIOR ELEVATIONS DON'T SHOW THE
 GUTTERS AND DOWNSPOUTS. PROVIDE REQUIRED INFORMATION.
 SPECIFY SIZES., ETC.
  
 9- REVISE ALL THE SCUPPERS DETAILS AND SPECIFICATIONS
 SHOWN ON SHEET S.1 TO SHOW COMPLIANCE WITH SEC. R903.4
 AND R903.4.1 FOR THE MAIN SCUPPER AND EMERGENCY
 SCUPPER. REVISE LOCATION OF MAIN SCUPPER AND LOCATION
 OF SECONDARY SCUPPER BASED ON THE LEVEL OF THE ROOF
 FINISHED SURFACE. NOTE: THE MAIN SCUPPER NEEDS TO BE
 LEVEL WITH THE ROOF SURFACE. REVISE ALL DETAILS TO
 MATCH.
  
 10- SECOND FLOOR DEN/BEDROOM DOESN'T COMPLY WITH THE
 MINIMUM ROOM AREA AND MINIMUM ROOM DIMENSION REQUIRED
 BY SEC. R304 FBC-RESIDENTIAL.
  
 11- WINDOWS IN ALL BATHROOMS ARE LOCATED IN HAZARDOUS
 LOCATIONS. PROVIDE COMPLIANCE WITH THE REQUIREMENTS OF
 SEC. R308.4 FBC-RESIDENTIAL.
  
 12- ALL THE SECOND FLOOR OPERABLE WINDOWS THAT HAVE
 WINDOW SILL LESS THAN 24" FROM THE FINISH FLOOR NEED TO
 SHOW COMPLIANCE WITH THE WINDOW FALL PROTECTION
 REQUIREMENTS OF SEC. R312.2 FBC-RESIDENTIAL. PROVIDE
 COMPLIANCE. AND, CLEARLY IDENTIFY ALL WINDOWS WITH
 WINDOW SILL LESS THAN 24" FROM THE FINISH FLOOR.
  
 13- FIRST FLOOR BATHROOM NEEDS TO HAVE A DOOR THAT
 PROVIDES 29" MINIMUM CLEAR OPENING AS REQUIRED BY SEC.
 R20 FBC-RESIDENTIAL. REVISE SIZE OF DOOR AS REQUIRED.
  
 14- WINDOW AND DOOR SCHEDULE ON SHEET S.2 AND ROOF
 PRESSURES ON SHEET S.5: CLARIFY IF THE DESIGN PRESSURES
 SPECIFIED ARE THE ULTIMATE DESIGN LOADS OR NOMINAL
 DESIGN LOADS. SEC. R301.2.1 FBC-RESIDENTIAL. NOTE:
 PRODUCT APPROVALS WILL BE REVIEWED ONCE THIS ISSUE IS
 CLARIFIED.
  
 15- WALL SECTIONS SPECIFY R-30 IMPERMEABLE INSULATION.
 PROVIDE IMPERMEABLE INSULATION ICC EVALUATION REPORT.
 NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING THE REPORT PRIOR TO SUBMITTAL. SEC. R316
 FBC-RESIDENTIAL.
  
 16- PROVIDE MANUFACTURER'S SPECS FOR THE SPECIFIC
 EGRESS WINDOWS SIZE SPECIFIED ON PLANS FOR THE SECOND
 FLOOR TO VERIFY COMPLIANCE WITH EGRESS. NOTE: NOT ALL
 25 SINGLE HUNG WINDOWS COMPLY WITH ALL THE EGRESS
 REQUIREMENTS FOR SECOND FLOOR WINDOWS. THAT'S WHY
 SPECIFIC SIZE AND MANUFACTURER'S CUT SHEETS ARE
 REQUIRED TO VERIFY COMPLIANCE. SEC. R310
 FBC-RESIDENTIAL.
  
 17- CLEARLY SHOW LOCATION OF HANDRAILS ON PROPOSED
 FLOOR PLANS ON SHEET S.2 AND WALL SECTIONS ON SHEET S.3
 AND SHEET S.4 SHOWING COMPLIANCE WITH SEC. R311.7.8
 FBC-RESIDENTIAL.
  
 18- VALUATION DECLARED IN THE PERMIT APPLICATIONS IS
 TOO LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED.
  
 19- ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING CODE IN EFFECT IS THE 2017 FBC. NEED TO
 USE CURRENT FORM R405-2017. REVISE AS REQUIRED.
 SEC. 553 FLORIDA STATUTE.
  
 B) OWNER OR LEGALLY AUTHORIZED AGENT TO CERTIFY AT THE
 BOTTOM OF FORM AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER (604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) THIS BUILDING IS DESIGNED WITH AN UNVENTED ATTIC.
 SEE PLANS AND REVISED CEILING INFORMATION ON ITEM #10
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) ROOF INFORMATION ON PAGE 2 OF 4 IS INCORRECT. THE
 FLAT ROOF AREA IS NOT 670 S.F. AND THERE IS NOT GABLE
 AREA IN THIS BUILDING. REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) ORIENTATION OF WALLS, EXTERIOR INSULATED DOOR AND
 WINDOWS CAN NOT BE CHECK AT THIS TIME BECAUSE THERE IS
 NOT SITE PLAN OR SURVEY SHOWING LOCATION AND
 ORIENTATION OF PROPOSED BUILDING. THIS WILL BE CHECKED
 WHEN INFORMATION IS PROVIDED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 G) WINDOWS OVERHANG DEPTH AND OVERHANG SEPARATION IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 20- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOOR FLORIDA PRODUCT APPROVAL FL4904-R7
 SUBMITTED. NEED PRODUCT APPROVAL FOR CURRENT 2017 CODE
 VERSION AND PROVIDE LEGIBLE DRAWINGS.
  
 B) FLAT ROOF MODIFIED BITUMEN ROOF SYSTEM FLORIDA
 PRODUCT APPROVAL FL1654-R20 SUBMITTED: NEED PRODUCT
 APPROVAL FOR CURRENT 2017 CODE VERSION. AND, NEED TO
 SPECIFY WHICH APPROVED ASSEMBLY FROM PRODUCT APPROVAL
 SUBMITTED IS GOING TO BE INSTALLED. NOTE: IF SELECTED
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF
 ZONES, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL
 BE REQUIRED.
  
 C) SINGLE HUNG WINDOWS NOA 16-0714.02 SUBMITTED: THIS
 NOA IS FOR SMALL MISSILE IMPACT WINDOWS. IF SUBMITTING
 WINDOWS WITH IMPACT GLAZING, THEN NEED TO PROVIDE
 PRODUCT APPROVAL FOR WINDOWS FOR LARGE MISSILE IMPACT
 RESISTANCE AS REQUIRED BY SEC. R301.2.1.2
 FBC-RESIDENTIAL. NOTE: CLARIFIED IF INSTALLING
 NON-IMPACT WINDOWS OR IMPACT WINDOWS. PLANS CALL FOR
 NON-IMPACT WINDOWS. COORDINATE INFORMATION ON PLANS AND
 PRODUCT APPROVALS TO AVOID CONFLICTS/DELAYS
  
 D) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 21- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 22- STORM SHUTTERS NOA 17-0118.07 SUBMITTED. PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 NOTE:
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]