Plan Review Notes For Permit 18010496 |
Permit Number |
18010496 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-02-12 16:52:05 | 1ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODES | | PERMIT #18010496 | | 2/12/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED TO | | VERIFY COMPLIANCE WITH SECTION 809.2 FBC-17 EXISTING | | BUILDING AND TABLE 403.1.1 FBC-17 MECHANICAL. | | | | 2) MISSING FIRE DAMPERS FOR DUCTS PENETRATING | | FIRE-RATED SEPARATION WALLS AT: ROOMS- 220/230, | | 225/230, 225/233, 251/239, CORRIDOR 203/212, 208/249, | | AND AT THE RETURN AIR GRILL AND THE EXISTING DUCT AT | | THE MECHANICAL ROOM WALLS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|