2018-02-12 16:52:051ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #18010496
 2/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED TO
 VERIFY COMPLIANCE WITH SECTION 809.2 FBC-17 EXISTING
 BUILDING AND TABLE 403.1.1 FBC-17 MECHANICAL.
  
 2) MISSING FIRE DAMPERS FOR DUCTS PENETRATING
 FIRE-RATED SEPARATION WALLS AT: ROOMS- 220/230,
 225/230, 225/233, 251/239, CORRIDOR 203/212, 208/249,
 AND AT THE RETURN AIR GRILL AND THE EXISTING DUCT AT
 THE MECHANICAL ROOM WALLS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  